![Cairox SOLANO CEILING-N-100 Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/cairox/solano-ceiling-n-100/solano-ceiling-n-100_technical-documentation-manual_3391493010.webp)
10
Switch 4 on SW3 to the position “E” and then restart the system switching it off for 5
seconds. Each time
the device is switched off the heaters are being cooled for next 30 seconds.
Œ
Power supply 3x400V/50Hz
·
SOLANO CEILING-E-100 (min. 5x2,5 mm
2
) (Overcurrent B16)
·
SOLANO CEILING-E-150 (min. 5x4,0 mm
2
) (Overcurrent B20)
·
SOLANO CEILING-E-200 (min. 5x4,0 mm
2
) (Overcurrent B25)
•
Air curtain step switch with thermostat S-C (OMY 5x0,5mm
2
)
·
HEAT- heating mode
·
FAN - room thermostat deactivated
·
COOL - cooling mode
·
1;2;3
–
step switch
Ž
Door contact S-DS-MEC/ S-DS-MAG (door closed
–
contacts opened; door opened
–
contacts closed)
(OMY 2x0,5mm
2
)
ATTENTION: