En-17

(7)  Turn the power off.

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Sign “

”: Lights off

Pump down is completed.

NOTES:

•  To stop pump down, press the [PUMP DOWN] button (S130) again.
•  To start the pump down again after the compressor is automatically stopped due 

to an error, turn the power off and open the 3-way valves. Wait 3 minutes, turn the 

power on and start the pump down again.

•  When starting the operation after completion of the pump down, turn the power off, 

and then open the 3-way valves. Wait 3 minutes, turn the power on and perform a 

test run in Cooling operation mode.

•  If an error occurs, recover the refrigerant from service port.

10. ERROR CODES

You can determine the operating status by the lighting on and blinking of the LED display.

S134

S133

S132

S131

S130

LED display part

Button part

10.1. Error display mode

Display when an error occurs.

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Blink 

(Hi speed)

Sign “

”: Lights off, “

”: Lights on

(1)  Check that the “ERROR” LED blinks, then press the [ENTER] button (S132) once.

9.1. Preparation for pump down

• Con

fi

 rm that the power is off, and then open the service panel.

9.2. Pump down procedure

(1)  Check the 3-way valves (both the liquid side and gas side) are opened.
(2)  Turn the power on.

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Sign “

”: Lights off, “

”: Lights on

(3)  Press [PUMP DOWN] button (S130) for 3 seconds or more after 3 minutes after 

power on.

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Sign “

”: Lights off, “

”: Lights on

LED display lights on as shown in the above table, and the fans and the 
compressor start operating.

•  If the [PUMP DOWN] button (S130) is pressed while the compressor is operating, 

the compressor will stop, then start again in about 3 minutes.

(4)  LED display will change as shown below about 3 minutes after the compressor 

starts. Fully close the 3-way valve on the liquid pipe side at this stage.

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Sign “

”: Lights off, “

”: Lights on

•  If the valve on the liquid pipe side is not closed, the pump down cannot be performed.

(5)  When LED display changes as shown in the following table, close the 3-way valve 

on the gas pipe side tightly. 

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Sign “

”: Lights off, “

”: Lights on

•  If the valve on the gas pipe side is not closed, refrigerant may 

fl

 ow into the piping 

after the compressor stops.

Step (5)

Closing direction

Step (4)

Hexagon wrench

Liquid pipe

Gas pipe

Closing direction

(6)  LED display changes after 1 minute as shown in the table.

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Sign “

”: Lights off, “

”: Lights on

Fans and compressor stop automatically.

•  If the pump down is successfully completed (the above LED display is shown), the 

outdoor unit remains stopped until the power is turned off.

9379069953_IM.indb   17

9379069953_IM.indb   17

5/24/2019   9:59:21 AM

5/24/2019   9:59:21 AM

Содержание AOYG-KQTA

Страница 1: ...Children should be supervised to ensure that they do not play with the appliance CAUTION For the air conditioner to work appropriately install it as written in this manual This product must be instal...

Страница 2: ...copper pipe work If a leak is suspected all naked flames shall be removed extinguished If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from the sy...

Страница 3: ...issioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed...

Страница 4: ...the units are further apart than this correct operation cannot be guaranteed Single type installation Capacity Btu h class 30 000 1 36 000 45 000 54 000 Pipe diameter Liquid Gas Standard mm in 9 52 3...

Страница 5: ...rom rain or direct sunlight If the outdoor unit must be installed in an area within easy reach of the general pub lic install as necessary a protective fence or the like to prevent their access Instal...

Страница 6: ...ations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs...

Страница 7: ...Slit Fig B Fig C 3 5 2 Pipe connection Brazing CAUTION If air or another type of refrigerant enters the refrigeration cycle the internal pressure in the refrigeration cycle will become abnormally high...

Страница 8: ...ealing test again 7 After completing the sealing test release the nitrogen gas from both valves 8 Release the nitrogen gas slowly When using conventional flare tools to flare R410A pipes the dimension...

Страница 9: ...wires make sure the power supply is off Never touch electrical components immediately after the power supply has been turned off Electrical shock may occur After turning off the power always wait 10...

Страница 10: ...l will be displayed and the unit will be inoperable 3 8 1 How to connect wiring to the terminal Caution when wiring cable When stripping off the coating of a lead wire always use a special tool such a...

Страница 11: ...connect it securely Firmly secure cable clamp so wire terminations will not receive external stress Connection cable Power supply cable Indoor unit Earth Ground Three phase type Terminal blocks Use t...

Страница 12: ...re control will not activate during test operation continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then energize the cra...

Страница 13: ...cause a serious accident such as electric shock CAUTION Once refrigerant charging is completed be sure to open the valve prior to performing the local settings Otherwise the compressor may fail Discha...

Страница 14: ...ing on the operating condition the noise level may not decrease even if the Low noise mode is on Level 2 Blink 9 times 2 Peak cut mode setting Level 1 Blink 9 times The capacity limit can be selected...

Страница 15: ...rning to Operation status displays normal operation by pressing the EXIT button once 8 EXTERNAL INPUT AND OUTPUT 8 1 External input 8 1 1 Wiring of connector On Off of the Low noise mode and Peak cut...

Страница 16: ...the button on the display board It may cause a serious accident such as electric shock During the pump down operation make sure that the compressor is turned off before you remove the refrigerant pipi...

Страница 17: ...ss PUMP DOWN button S130 for 3 seconds or more after 3 minutes after power on POWER MODE ERROR PUMP DOWN LOW NOISE PEAK CUT L1 L2 L3 L4 L5 L6 Sign Lights off Lights on LED display lights on as shown i...

Страница 18: ...error Outdoor temp sensor error Blink 2 times Blink 7 times Blink 4 times Heat sink temp sensor error Heat sink temp sensor error Blink 2 times Blink 7 times Blink 7 times Current sensor error Curren...

Отзывы: