En-14

7. FIELD SETTING

CAUTION

•  Discharge the static electricity from your body before setting up the switches.
•  Never touch the terminals or the patterns on the parts that are mounted on the 

board.

7.1. Field setting buttons

•  Remove the front panel of the outdoor unit to access the print circuit board of the 

display  unit.
Print circuit board buttons for various settings and LED displays are shown in the 

fi

 gure. 

S134

S133

S132

S131

S130

LED display part

Button part

 7.2. Function settings

•  Various functions can be set. Follow the setting method described in 7.2.1. and 7.2.2. to set as per the requirement.

Perform these settings after the indoor unit stops.

Table. Settings List

No

Setting Item

LED display

Factory 

setting

Content

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

1

Low noise 

mode setting

Level 1

Blink 

(9 times)

By using the “Low noise mode”, the limit of the 

noise level will be set to decrease the noise 

level. The mode comes in 2 levels which can 

be set accordingly.

To turn on the mode, use the external input 

connector (P580).

*By using this mode, the cooling/heating 

performance may decrease.

*Depending on the operating condition, the 

noise level may not decrease even if the Low 

noise mode is on.

Level 2

Blink 

(9 times)

2

Peak cut 

mode setting

Level 1

Blink 

(9 times)

The capacity limit can be selected when 

operating with the Peak cut mode. The 

operation selection can be done by external 

input connector (PA580).

The lower the level, the more the effect of 

energy saving, but the cooling/heating perfor-

mance decreases.

Level 2

Blink 

(9 times)

Level 3

Blink 

(9 times)

Level 4

Blink 

(9 times)

Sign “

”: Lights off, “

”: Lights on

7.2.1. Setting for Low noise mode

(1)  Switch to “Local setting mode” by pressing [MODE] button (S134) for 3 seconds or 

more.

(2) Con

fi

 rm (POWER / MODE) blinks 9 times, and press [ENTER] button (S132).

POWER/

MODE

ERROR

PUMP 

DOWN

LOW  NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Blink

(9 times)

Sign “

”: Lights off, “

”: Lights on, () : Number of blinking

(3)  Press [SELECT] button (S133), and adjust LED display as shown below. (Current 

setting is displayed)

LOW NOISE

(L2)

(L3)

LOW NOISE

MODE

Blink

Sign “

”: Lights off

(4)  Press [ENTER] button (S132).

LOW NOISE

(L2)

(L3)

LOW NOISE

MODE

Sign “

”: Lights off, “

”: Lights on

(5)  Press [SELECT] button (S133), and adjust LED display as shown in below 

fi

 gure.

PEAK CUT

(L4)

(L5)

(L6)

Level 1

Blink

Level 2

Blink

Sign “

”: Lights off

The noise of Level 2 is lower than the one of Level 1.

9379069953_IM.indb   14

9379069953_IM.indb   14

5/24/2019   9:59:20 AM

5/24/2019   9:59:20 AM

Содержание AOYG-KQTA

Страница 1: ...Children should be supervised to ensure that they do not play with the appliance CAUTION For the air conditioner to work appropriately install it as written in this manual This product must be instal...

Страница 2: ...copper pipe work If a leak is suspected all naked flames shall be removed extinguished If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from the sy...

Страница 3: ...issioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed...

Страница 4: ...the units are further apart than this correct operation cannot be guaranteed Single type installation Capacity Btu h class 30 000 1 36 000 45 000 54 000 Pipe diameter Liquid Gas Standard mm in 9 52 3...

Страница 5: ...rom rain or direct sunlight If the outdoor unit must be installed in an area within easy reach of the general pub lic install as necessary a protective fence or the like to prevent their access Instal...

Страница 6: ...ations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs...

Страница 7: ...Slit Fig B Fig C 3 5 2 Pipe connection Brazing CAUTION If air or another type of refrigerant enters the refrigeration cycle the internal pressure in the refrigeration cycle will become abnormally high...

Страница 8: ...ealing test again 7 After completing the sealing test release the nitrogen gas from both valves 8 Release the nitrogen gas slowly When using conventional flare tools to flare R410A pipes the dimension...

Страница 9: ...wires make sure the power supply is off Never touch electrical components immediately after the power supply has been turned off Electrical shock may occur After turning off the power always wait 10...

Страница 10: ...l will be displayed and the unit will be inoperable 3 8 1 How to connect wiring to the terminal Caution when wiring cable When stripping off the coating of a lead wire always use a special tool such a...

Страница 11: ...connect it securely Firmly secure cable clamp so wire terminations will not receive external stress Connection cable Power supply cable Indoor unit Earth Ground Three phase type Terminal blocks Use t...

Страница 12: ...re control will not activate during test operation continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then energize the cra...

Страница 13: ...cause a serious accident such as electric shock CAUTION Once refrigerant charging is completed be sure to open the valve prior to performing the local settings Otherwise the compressor may fail Discha...

Страница 14: ...ing on the operating condition the noise level may not decrease even if the Low noise mode is on Level 2 Blink 9 times 2 Peak cut mode setting Level 1 Blink 9 times The capacity limit can be selected...

Страница 15: ...rning to Operation status displays normal operation by pressing the EXIT button once 8 EXTERNAL INPUT AND OUTPUT 8 1 External input 8 1 1 Wiring of connector On Off of the Low noise mode and Peak cut...

Страница 16: ...the button on the display board It may cause a serious accident such as electric shock During the pump down operation make sure that the compressor is turned off before you remove the refrigerant pipi...

Страница 17: ...ss PUMP DOWN button S130 for 3 seconds or more after 3 minutes after power on POWER MODE ERROR PUMP DOWN LOW NOISE PEAK CUT L1 L2 L3 L4 L5 L6 Sign Lights off Lights on LED display lights on as shown i...

Страница 18: ...error Outdoor temp sensor error Blink 2 times Blink 7 times Blink 4 times Heat sink temp sensor error Heat sink temp sensor error Blink 2 times Blink 7 times Blink 7 times Current sensor error Curren...

Отзывы: