En-12

4. TEST RUN

4.1. Pre-test run check items

Check items

 Is the outdoor unit securely installed?

  Have you performed gas leakage inspection?

(Connection joints of various pipes (

fl

 ange connection, brazing))

  Is the heat insulation done completely?

(Gas pipe, liquid pipe, drain hose extension on indoor unit side etc.)

 Is the water discharging from drain without any problems?

 Are the cables connected correctly?

 Are the cables as per speci

fi

 cations?

 Is the earth (ground) wire connected accurately?

  Are there any obstacles blocking the suction gate, and outlet of 

the indoor/outdoor units?

 Have you 

fi

 lled the speci

fi

 ed amount of refrigerant?

 Are the stop valves of gas pipe and liquid pipe fully open?

 Has the power been supplied to crankcase heater for more than 6 hours?

 After checking that the above items are all in order, refer to “4.2. Test operation method” to 

test operation the unit. If there are problems, adjust immediately and recheck.

 4.2. Test operation method

Be sure to con

fi

 gure test run settings only when the outdoor unit has stopped oper-

ating.

Test operation setting method (It can be performed in the following two ways)

•  Set with test operation setting (refer to the installation manual of indoor unit for further 

details) available in the remote controller.

•  Cooling operation and Heating operation can be set using [SELECT] button (S133) 

and [ENTER] button (S132) available on the board of display unit. 

(Make sure to perform the 

fi

 rst test operation with cooling operation.) 

Set as per the following procedure.

S134

S133

S132

S131

S130

LED display part

Button part

• Depending 

on 

the 

communication 

status 

between the indoor and outdoor units, 

it may take several minutes for the system to start operating after settings for the 
test run are complete.

•  After the test run settings are complete, the outdoor units and the connected 

indoor units will start operating. Room temperature control will not activate during 
test operation (continuous operation).

•  If a knocking sound can be heard in the liquid compression of the compressor, 

stop the unit immediately and then energize the crank case heater for a suf

fi

 cient 

length of time before restarting the operation.

4.2.1. Setting method on outdoor unit board

(1)  

 

Turn on the power of the outdoor unit and enter standby mode. 
“POWER/MODE” display lights on.

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Sign “

”: Lights off, “

”: Lights on

(2)  Press the [ENTER] button (S132) for more than 3 seconds.

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Blink

Blink

Sign “

”: Lights off, “

”: Lights on

(3)  Press the [SELECT] button (S133), LED of the test run mode switched between 

Cooling and Heating.
Cooling test mode

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Blink

Blink

Sign “

”: Lights off, “

”: Lights on

Heating test mode

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Blink

Blink

Sign “

”: Lights off, “

”: Lights on

(4) After 

con

fi

 rming the operation mode, press [ENTER] button (S132).

The display changes as follows, and the air conditioner starts operation.
Cooling test mode

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Blink

Sign “

”: Lights off, “

”: Lights on

Heating test mode

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Blink

Sign “

”: Lights off, “

”: Lights on

(5)  Press [ENTER] button (S132).

Air conditioner stops operation.

POWER/

MODE

ERROR

PUMP 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Sign “

”: Lights off, “

”: Lights on

4.3. Checklist

Check items during test operation.

 Is the outdoor unit making any abnormal noise or vibrating signi

fi

 cantly?

  Is the cold air or hot air blowing from indoor unit according to the operation 

mode?

 Check that the “ERROR” LED blinks.

If, it has displayed, check the error content as per the “10.2. Error code check 
table” described later.

  Operate the unit according to the operating manual provided with the indoor 

unit, and check that it is operating normally.

9379069953_IM.indb   12

9379069953_IM.indb   12

5/24/2019   9:59:20 AM

5/24/2019   9:59:20 AM

Содержание AOYG-KQTA

Страница 1: ...Children should be supervised to ensure that they do not play with the appliance CAUTION For the air conditioner to work appropriately install it as written in this manual This product must be instal...

Страница 2: ...copper pipe work If a leak is suspected all naked flames shall be removed extinguished If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from the sy...

Страница 3: ...issioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed...

Страница 4: ...the units are further apart than this correct operation cannot be guaranteed Single type installation Capacity Btu h class 30 000 1 36 000 45 000 54 000 Pipe diameter Liquid Gas Standard mm in 9 52 3...

Страница 5: ...rom rain or direct sunlight If the outdoor unit must be installed in an area within easy reach of the general pub lic install as necessary a protective fence or the like to prevent their access Instal...

Страница 6: ...ations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs...

Страница 7: ...Slit Fig B Fig C 3 5 2 Pipe connection Brazing CAUTION If air or another type of refrigerant enters the refrigeration cycle the internal pressure in the refrigeration cycle will become abnormally high...

Страница 8: ...ealing test again 7 After completing the sealing test release the nitrogen gas from both valves 8 Release the nitrogen gas slowly When using conventional flare tools to flare R410A pipes the dimension...

Страница 9: ...wires make sure the power supply is off Never touch electrical components immediately after the power supply has been turned off Electrical shock may occur After turning off the power always wait 10...

Страница 10: ...l will be displayed and the unit will be inoperable 3 8 1 How to connect wiring to the terminal Caution when wiring cable When stripping off the coating of a lead wire always use a special tool such a...

Страница 11: ...connect it securely Firmly secure cable clamp so wire terminations will not receive external stress Connection cable Power supply cable Indoor unit Earth Ground Three phase type Terminal blocks Use t...

Страница 12: ...re control will not activate during test operation continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then energize the cra...

Страница 13: ...cause a serious accident such as electric shock CAUTION Once refrigerant charging is completed be sure to open the valve prior to performing the local settings Otherwise the compressor may fail Discha...

Страница 14: ...ing on the operating condition the noise level may not decrease even if the Low noise mode is on Level 2 Blink 9 times 2 Peak cut mode setting Level 1 Blink 9 times The capacity limit can be selected...

Страница 15: ...rning to Operation status displays normal operation by pressing the EXIT button once 8 EXTERNAL INPUT AND OUTPUT 8 1 External input 8 1 1 Wiring of connector On Off of the Low noise mode and Peak cut...

Страница 16: ...the button on the display board It may cause a serious accident such as electric shock During the pump down operation make sure that the compressor is turned off before you remove the refrigerant pipi...

Страница 17: ...ss PUMP DOWN button S130 for 3 seconds or more after 3 minutes after power on POWER MODE ERROR PUMP DOWN LOW NOISE PEAK CUT L1 L2 L3 L4 L5 L6 Sign Lights off Lights on LED display lights on as shown i...

Страница 18: ...error Outdoor temp sensor error Blink 2 times Blink 7 times Blink 4 times Heat sink temp sensor error Heat sink temp sensor error Blink 2 times Blink 7 times Blink 7 times Current sensor error Curren...

Отзывы: