A3484-A3485 AC/DC Converter 400 V 3-phase 48 V 2.5/5kW
04/07/2017
3
NPO:
Filename:
Number of pages:
Page:
00120/04:A348x.MUTx/03
A3485_REV3.DOC
21
11
2 AMP 280372-2 type connector (M/-)
1 Trimmer (Vout adjustment)
1 Bistable switch (CHANNEL ON/OFF)
1 green LED (CHANNEL ON)
2.1.3
EASY BUS
Fig. 2.4 – EASY BUS section
This section (available on Mod. A3484S/A3485S) provides the link for the module
connection with the A1676A and includes:
1 9 Pin DB-type male connector
2.1.4
Interlock
Fig. 2.5 – Interlock section
This section allows to enable/disable the module output and includes:
1 AMP 280372-2 type connector
1 red LED
The Interlock can work in two ways:
PASSIVE OPERATION:
it is necessary to short circuit pin 1 (“GND”, the first from left to
right) with pin 2 (“K=katode”), and pin 3 (“A=anode”) with pin 4 (“VCC”).
ACTIVE OPERATION: it is necessary to send a voltage level (for example a TTL; the
recommended current is about 10 mA) between pin 2 = katode and pin 3 = anode (high =
interlock disabled, the channel can be turned on; low = interlock enabled, the channel
cannot be turned on), leaving pin 1 and pin 4 disconnected.
The LED is ON when the Board is enabled.