Document type:
Title:
Revision date:
Revision:
User's Manual (MUT)
A3484-A3485 AC/DC Converter 400 V 3-phase 48 V 2.5/5kW
04/07/2017
3
NPO:
Filename:
Number of pages:
Page:
00120/04:A348x.MUTx/03
A3485_REV3.DOC
21
19
A read access to the
V0set#HighEU
item returns the highest possible V0set value.
A read access to the
V0set#LowEU
item returns the lowest possible V0set value.
The
I0set
item allows to set I0.
A read access to the
I0set#EU
item returns a string with the I0set Engineering Units.
A read access to the
I0set#HighEU
item returns the highest possible I0set value.
A read access to the
I0set#LowEU
item returns the lowest possible I0set value.
The
Trip
item allows to program the trip time.
A read access to the
Trip#EU
item returns a string with the Trip Engineering Units.
A read access to the
Trip#HighEU
item returns the highest possible Trip value.
A read access to the
Trip#LowEU
item returns the lowest possible Trip value.
The
SVMax
item allows to set the software voltage limit.
A read access to the
SVMax#EU
item returns a string with the SVMax Engineering Units.
A read access to the
SVMax#HighEU
item returns the highest possible SVMax value.
A read access to the
SVMax#LowEU
item returns the lowest possible SVMax value.
The
VMon
item returns back the VMon value.
A read access to the
VMon#EU
item returns a string with the VMon Engineering Units.
A read access to the
VMon#HighEU
item returns the highest possible VMon value.
A read access to the
VMon#LowEU
item returns the lowest possible VMon value.
The
VCon
item returns back the VCon value.
A read access to the
VCon#EU
item returns a string with the VCon Engineering Units.
A read access to the
VCon#HighEU
item returns the highest possible VCon value.
A read access to the
VCon#LowEU
item returns the lowest possible VCon value.
The
IMon
item returns back the IMon value.
A read access to the
IMon#EU
item returns a string with the IMon Engineering Units.
A read access to the
IMon#HighEU
item returns the highest possible IMon value.
A read access to the
IMon#LowEU
item returns the lowest possible IMon value.
The
Temp
item returns back the channel temperature.
A read access to the
Temp#EU
item returns a string with the Temp Engineering Units.
A read access to the
Temp#HighEU
item returns the highest possible Temp value.
A read access to the
Temp#LowEU
item returns the lowest possible Temp value.
A read access to the
Status
item returns back a 16 bit pattern indicating channel status,
as follows:
Bit 0: ON/OFF
Bit 1: don’t care
Bit 2: don’t care
Bit 3: OverCurrent
Bit 4: OverVoltage
Bit 5: UnderVoltage
Bit 6: don’t care
Bit 7: Over HVmax
Bit 8: don’t care
Bit 9: Internal Trip
Bit 10: Calibration Error
Bit 11: don’t care
Bit 12: don’t care
Bit 13: OverVoltage Protection
Bit 14: Power Fail
Bit 15: Temperature Error
The
RemIlk
item returns back the Remote Interlock value.