Page 7
509 Sharptown Road P.O. Box 345 Bridgeport, NJ 08014
Email: [email protected] Fax: 856-467-5511
Internet: http://caddycorp.com Phone: 856-467-4222
Electrical Fire Fuel Connections
Installation
Route three wires in ½" conduit (as shown on drawing) from the micro-switch in the fire control system (by others) to
the equipment shut-off terminal block (red) in the Utility Distribution System.
DO NOT
remove any existing wires
from terminals. Connect wires to the UNUSED posts of the Red terminal block as follows:
a.
Connect the neutral wire to the terminal with the White wire.
b.
Locate wire which supplies 120 volts during normal operating conditions (and is switched OFF when
fire control system is activated), and connect this to the terminal with the Black wire.
c.
Locate wire which supplies 120 volts when fire control system is activated, and connect this to the
terminal with the Red wire.