ELECTRODE WIRE REPLACEMENT

1 .  Remove front panel (see 

FIGURE 2

) .

2 .  Remove side panel (see 

FIGURE 2

) .

3 .  Remove the electrode wires (see 

FIGURE 3A

 and 

FIGURE 3B

) . 

a .  For units with one circuit board: Use needle nose pliers to pull the 

spade connectors off spade terminals J8 and J10 on the circuit board .

b .  For units with two circuit boards: Use needle nose pliers to pull the 

spade connectors off the spade terminals on the power relay .

4 .  Ensure the two replacement electrode wires (Part #5372) have “O” 

shape connectors (see 

FIGURE 4B

) . 

Do not use replacement wires 

with “D” shape connectors

 (see 

FIGURE 4A

) .

5 .  Attach the new electrode wires (see 

FIGURE 3A

 and 

FIGURE 3B

) . 

a .  For units with one circuit board: Use a pair of needle nose pliers to 

attach the spade connectors to the spade terminals J8 and J10 on 
the circuit board . Electrode wires are interchangeable and can be 
placed on either of the two terminals .

b .  For units with two circuit boards: Use a pair of needle nose pliers to 

attach the connectors to the spade terminals on the power relay . 

One 

wire, either one but not both, must go through current-sensing 
toroid

 (see 

FIGURE 3A

) . Electrode wires are interchangeable and 

can be placed on either of the two terminals .

FILL VALVE SERVICE

1 .  Disconnect water supply line from fill valve inlet (see 

FIGURE 5

) .

2 .  Remove in-line strainer from the fill valve inlet port using a #8 or #10 

sheet metal or wood screw with a minimum length of 0 .5” .

3 .  Clean or replace in-line strainer (Part #4358) .
4 .  Reconnect water supply line to fill valve inlet (see 

FIGURE 5

) .

RESTORE UNIT TO SERVICE

1 .  Replace side panel if removed (see 

FIGURE 2

) .

2 .  Replace front panel (see 

FIGURE 2

) .

3 .  Inspect drain hose to make sure it is not blocked and has constant 

downward slope . Clean or replace if necessary .

4 .  Inspect and clean condensate pump (if used) .
5 .  Inspect steam hose to make sure it has no low spots and has constant 

upward slope from humidifier to dispersion tube in duct . If dispersion 
tube is mounted below humidifier, inspect drip tee and drain trap .

6 .  Restore main electrical power to humidifier at circuit breaker .
7 .  Turn humidifier on and verify green 

On/Off

 light is illuminated (see 

FIGURE 2

) .

8 .  Check system operation and inspect all plumbing connections and piping 

for signs of cracks or leaks .

Содержание HUM STM3034 Series

Страница 1: ...READ AND SAVE THESE INSTRUCTIONS Model HUMCRSTM3134 HUMXXSTM3034 HUMXXSTM3134 Residential Steam Humidifier Owner s Manual Includes Safety Operating Instructions Residential Steam Humidifier...

Страница 2: ...until electrical power is disconnected Follow the shutdown procedure in this manual before performing service or maintenance procedures on any part of the system ELECTRICAL SHOCK HAZARD If the humidif...

Страница 3: ...and Canister 90 1522 Steam Outlet Drain Supply Water Drain Cup Drain Valve Canister Electrodes High Water Level Sensor Flow Control Orifice Inlet Fill Valve Overflow Fill Fill Cup Thank you for your...

Страница 4: ...s time the Steam light illuminates green If the humidifier cannot produce steam at the rated level after trying for 168 hours the Steam light illuminates yellow The humidifier continues to operate in...

Страница 5: ...ent level below 75 of the maximum operating current Humidifier continues to operate but at reduced capacity Solid Red Operational problem with humidifier Humidifier shuts down Occurs when unit detects...

Страница 6: ...HOCK HAZARD Disconnect main electrical power to the humidifier at the circuit breaker and drain the water from unit before servicing Hot surface inside NOTICE Service should be performed by an HVAC te...

Страница 7: ...w O ring O ring is provided with Model 8045HUM canister into slot in drain assembly Dampen O ring with water before inserting canister Do not use oil grease or any lubricant besides water 12 Make sure...

Страница 8: ...er relay One wire either one but not both must go through current sensing toroid see FIGURE 3A Electrode wires are interchangeable and can be placed on either of the two terminals FILL VALVE SERVICE 1...

Страница 9: ...Catalog No OM HUMCRSTM 02 10016625 B2210113B 02 23 2023 CAC BDP 7310 West Morris St Indianapolis IN 46231...

Отзывы: