background image

6

CLEARANCES -- INDOOR

 ≥35mm

≥1000mm

≥ 35mm

≥ 35mm

A0150267

Fig. 8 – 40MKCB**F, 40MKQB**F Unit Clearance

CLEARANCES -- OUTDOOR

1.

Single Unit Applications:

With coil facing wall: Allow 6”

(152.4mm) minimum clearance on coil side and coil end and
20” (504.0 mm) minimum clearance on fan side. Allow 24”

(609.6 mm) minimum clearance on compressor end for
service.

2.

With fan facing wall:

Allow 8” (203.2 mm) minimum

clearance on fan side and coil end and 20” (504.0 mm)
minimum clearance on coil side. Allow 24” (609.6 mm)

minimum clearance on compressor end for service when units
are stacked or there is less than 40” (1016 mm) of clearance
above the unit. If there is 40” (1016 mm) clearance above unit

and the top panel is accessible for removal allow 8” (203.2
mm) minimum clearance on compressor end for service.

3.

Multi--unit Applications:

Allow 24” (609.6 mm) minimum

clearance between fan and coil sides of multiple units. Arrange
units so discharge of one does not enter inlet of another. Allow

24” (609.6 mm) minimum clearance on compressor end when
units are stacked or there is less than 40” (1016 mm) of

clearance above the unit. If there is 40” (1016 mm) clearance
above unit and the top panel is accessible for removal allow 8”

(203.2 mm) minimum clearance on compressor end for
service. When two units are installed end to end with the coil
ends facing each other allow 12” (304.8 mm) minimum

clearance between units.

IMPORTANT: When installing multiple units, ensure the
discharge air from one unit is not drawn into another unit.
When installing single or multiple units in an alcove, roof well,
or partially enclosed area, ensure there is adequate ventilation
to prevent recirculation of discharge air.

SYSTEM REQUIREMENTS

Clearances

Allow sufficient space around the indoor and outdoor unit for

proper airflow circulation and servicing. Refer to Fig.8 and the

outdoor unit clearance section for minimum required clearances.

Piping:

Piping and insulation is field supplied.

Piping Lengths

The minimum length between the indoor and outdoor units is 10 ft

(3 m). Refer to table 9 for the maximum lengths allowed.

Table 9 – Maximum Refrigerant Line Lengths

Unit Size

Max Line

Length* ft(m)

Max elevation (ID

over OD ft (m)

Max Elevation

(OD over ID) ft

(m) ft (m)

18K -54K

250 (76.2)

65 (19.8)

200 (61)

Note

:

For lengths greater than 25 ft (7.6 m), refer to the

Residential Long

Line Guide

.

Pipe Sizes

In some models, indoor unit and/or outdoor unit pipe sizes may

differ from those in TXV connections. Coupling is required in

those cases. See table below for a complete list of tube sizes to

identify coupling needs. Refer to Table 10 for pipe sizes.

Table 10 – Pipe Sizes

Indoor Units

Outdoor Units

Indoor Unit Tube

Sizes (in)

TXV Kit Tube

Sizes (in)

Outdoor Unit Tube

Size (in)

Liquid

Vapor

Liquid

Vapor

Liquid

Vapor

40MKCB18F----3

24AHA418

124ANS018

3/8

5/8

3/8

5/8

3/8

5/8

40MKCB34F----3

24AHA424

124ANS024

3/4

3/4

3/4

40MKCB34F----3

24AHA430

124ANS030

3/4

3/4

3/4

40MKCB34F----3

24AHA436

124ANS036

3/4

3/4

7/8

40MKCB54F----3

24AHA448

124ANS048

3/4

7/8

7/8

40MKQB36F----3

25HHA430224A

NS030

3/4

3/4

3/4

40MKQB36F----3

25HHA436

224ANS036

3/4

3/4

7/8

40MKQB48F----3

25HHA448

224ANS048

3/4

7/8

7/8

Note

:

Both lines need to be insulated using at least 1/2 inch closed

foam insulation.

Содержание 40MKCB**F/24AHA4

Страница 1: ...aller service agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this product Refer to...

Страница 2: ...Only 018 24AHA418A003 124ANS018000 40MKCB18F 3 024 24AHA424A003 124ANS024000 40MKCB34F 3 030 24AHA430A003 124ANS030000 40MKCB34F 3 034 24AHA436A003 5 6 124ANS036000 40MKCB34F 3 054 24AHA448A003 5 6 12...

Страница 3: ...ONS INDOOR Unit W D H Hook D W Bracket A0150266 Fig 6 440MKCB F 40MKQB F Unit and Bracket Dimensions Table 4 Dimensions Indoor Indoor Unit Size BTU Hr Height H in mm Width W in mm Depth D in mm Operat...

Страница 4: ...4 DIMENSIONS OUTDOOR Fig 7 Outdoor Unit Dimensions NOTE S Center of Gravity S All dimensions are in inches unless noted UNIT SIZE MINIMUM MOUNTING PAD DIMENSIONS 18 24 23 x 42 30 36 48 24 x 50...

Страница 5: ...NS030000 124ANS036000 124ANS048000 Table 7 Dimensions SI ACs 124ANS018000 124ANS024000 124ANS030000 124ANS036000 124ANS048000 Table 8 Dimensions HPs 2 224ANS030000 224ANS036000 224ANS048000 Table 9 Di...

Страница 6: ...nstalling single or multiple units in an alcove roof well or partially enclosed area ensure there is adequate ventilation to prevent recirculation of discharge air SYSTEM REQUIREMENTS Clearances Allow...

Страница 7: ...g cable consists of three 3 wires Two wires are high voltage AC power and one is a ground wire Consult your local building codes and the NEC National Electrical Code or CEC Canadian Electrical Code fo...

Страница 8: ...stall indoor units near a direct source of heat such as direct sunlight or a heating appliance S Do not install units too close to humid conditions S Where an optimum air distribution is ensured S Whe...

Страница 9: ...TXV kit Flexible piping is recommended CAUTION Failure to follow the following caution may result in equipment damage or improper operation Insulate liquid and vapor pipes connecting to indoor and out...

Страница 10: ...to each suspension bolts making space for hanging the indoor unit S Hang the indoor unit to the suspension bolts between two nuts see Fig 18 S Screw the nuts to suspend the unit S Adjust level of the...

Страница 11: ...adient of 2 without obstruction see Fig 20 DO NOT install the drainpipe to an upward position It may cause water to flow back to the unit S Make a trap of at least 2 in 51 mm in depth to prevent unple...

Страница 12: ...y damage the compressor at start up When more than 80 ft 24 4 m of interconnecting tubing is used consult the Residential Long Line Application Guide for required accessories 3 Insulate both lines A m...

Страница 13: ...njury or death Before performing service or maintenance be sure indoor unit main power switch is turned OFF and indoor blower has stopped Lock out and tag switch with a suitable warning label Power Wi...

Страница 14: ...the unit side panel and connect to the control terminal strip using either Fig 28 for AC units or Fig 29 for Heat Pump units A150280 Fig 28 40MKCB F 24AHA4 or 124ANS Connecting diagram A150282 Fig 29...

Страница 15: ...0 208 230 3 253 197 71 9 3 1 2 12 8 20 48 50 83 1 13 7 1 45 18 6 30 36 60 460 3 506 414 38 5 6 0 6 7 6 15 48 60 41 6 2 0 8 8 6 15 Table 19 40MKCB F Electrical Data Indoor Unit Size BTU Hr V Ph Hz Volt...

Страница 16: ...r Live wire L1 Nullline L2 interface 24V interface CN 20 Network module interface CN 12 Vertical swing motor interface CN 13 horizontalswing motor interface CN 10 Display boardinterface CN 15 Compress...

Страница 17: ...LivewireL1 NulllineL2 interface 24V interface CN20 Networkmodule interface CN12 Ver ticals wingmotor interface CN13 horizontalswingmotor interface CN10 Disp layboardinterface CN15 Sign alinterface Y...

Страница 18: ...nect switch to the unit s control box Use copper wire only between the disconnect switch and unit 5 If any accessories are being installed refer to the individual accessory instructions for guidance o...

Страница 19: ...ect manifold gage charge hose to a charge port of the low side service valve see Fig 40 2 Connect charge hose to vacuum pump 3 Fully open the low side of manifold gage see Fig 41 4 Start vacuum pump 5...

Страница 20: ...t mode the unit will run in cooling and heating on heat pumps regardless if there is demand or not TEST OPERATION FOR UNDER CEILING CONSOLE Perform test operation after completing gas leak and electri...

Страница 21: ...down Procedure The system may be pumped down in order to make repairs on the low side without losing complete refrigerant charge 1 Attach pressure gage to suction service valve gage port 2 Front seat...

Страница 22: ...s NO Malfunction Running lamp Timer lamp Defrosting lamp Alarm lamp Display digital tube 1 Open or short circuit of T1 temperature sensor X X X E2 2 Open or short circuit of T2 temperature sensor X X...

Страница 23: ...w or too high Check temperature setting Outdoor unit fan faulty Replace outdoor fan Air or other non condensable gasses in the circuit Drain refrigerant evacuate and recharge CAUTION Do not vent refri...

Страница 24: ...P D 7310 W Morris St D Indianapolis IN 46231 Edition Date 07 15 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MKC...

Отзывы: