background image

23

Table 22 – Troubleshooting

PROBLEM

POSSIBLE CAUSE

SOLUTION

Compressor and Fan of the Outdoor

Unit Will Not Start

Unit not energized

Check the main power connection.

Main switch is set to OFF

Check and put it to ON position.

Main switch fuses are blown

Replace fuses.

Compressor cycling protection is on

Wait for 3 minutes.

Main power voltage is too low

Check and set to the correct voltage.

Electrical connections are too loose or are wrong

Check and tighten or correct connections.

Compressor Will Not Start, But

Outdoor Fan is Operating

Electrical connections of compressor are loose or

wrong

Check and tighten or repair compressor.

Compressor Stops Due to

Over---temperature

Compressor burnt out; seized or protection device

on

Check for the cause and replace compressor if

necessary.

Wrong refrigerant charge in unit (excessive or low)

or air or other non---condensable gasses in the

circuit

Drain refrigerant, evacuate and recharge.

CAUTION

: Do not vent refrigerant to the atmosphere; use

refrigerant recovery equipment.

Main voltage is too high or too low

Check voltage setting and adjust if necessary.

Condenser coil obstructed

Remove obstruction.

Outdoor fan off

Check cause and resume operation or repair.

Wrong indoor unit thermistors

Replace thermistors.

Refrigerant circuit clogged

Check and remove obstructions.

Reversing valve faulty on heat pump models

Replace reversing valve.

Expansion device clogged or covered with ice

Drain refrigerant, evacuate and recharge.

CAUTION

: Do not vent refrigerant to the atmosphere; use

refrigerant recovery equipment.

Compressor Runs Continuously

Unit selected is too small for application

requirements

Contact a qualified service technician for a system

evaluation.

Indoor temperature setting too low or too high

Check temperature setting.

Outdoor unit fan faulty

Replace outdoor fan.

Air or other non---condensable gasses in the

circuit

Drain refrigerant, evacuate and recharge.

CAUTION

: Do not vent refrigerant to the atmosphere; use

refrigerant recovery equipment.

Obstructions at air intake or dirty indoor unit filters

Remove obstruction and/or clean filter.

Frequent Ice---Build---Up on Outdoor

Coil

Outdoor fan is stopped

Check cause and repair.

Discharge Pressure Too High

Outdoor coil dirty or obstructed

Clean or remove obstructions.

Condenser fan faulty

Replace condenser fan.

Indoor temperature setting too low or too high

Check temperature setting.

Air or other non---condensable gasses in the

circuit

Drain refrigerant, evacuate and recharge.

CAUTION

: Do not vent refrigerant to the atmosphere; use

refrigerant recovery equipment.

Discharge Pressure Too Low

Indoor temperature setting too high or too low

Check temperature setting.

Outdoor coil dirty or obstructed

Clean or remove obstructions.

Indoor unit air filter dirty

Clean filter.

Suction Pressure Too High

Indoor temperature setting too high or too low

Check temperature setting.

Reversing valve faulty or internal leak

Replace reversing valve.

Suction Pressure Too Low

Indoor temperature setting too high or too low

Check temperature setting.

Evaporator coil covered with ice

Air circulation on the evaporator not sufficient; check and

repair.

Expansion device or suction line clogged

Check and repair.

Outdoor fan does not stop during defrost periods

Check electrical parts.

Outdoor Fan Cycling Due to

Over---Temperature Protection

Electrical connection loose

Check connections.

Fan motor burn out

Replace.

Fan bearing seized

Check and repair.

Expansion device clogged or covered with ice

Drain refrigerant, evacuate and replace.

CAUTION:

Do not vent refrigerant to the atmosphere; use

refrigerant recovery equipment.

NOTE

:

For additional diagnostic information, refer to the “Service Manual”.

Содержание 40MKCB**F/24AHA4

Страница 1: ...aller service agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this product Refer to...

Страница 2: ...Only 018 24AHA418A003 124ANS018000 40MKCB18F 3 024 24AHA424A003 124ANS024000 40MKCB34F 3 030 24AHA430A003 124ANS030000 40MKCB34F 3 034 24AHA436A003 5 6 124ANS036000 40MKCB34F 3 054 24AHA448A003 5 6 12...

Страница 3: ...ONS INDOOR Unit W D H Hook D W Bracket A0150266 Fig 6 440MKCB F 40MKQB F Unit and Bracket Dimensions Table 4 Dimensions Indoor Indoor Unit Size BTU Hr Height H in mm Width W in mm Depth D in mm Operat...

Страница 4: ...4 DIMENSIONS OUTDOOR Fig 7 Outdoor Unit Dimensions NOTE S Center of Gravity S All dimensions are in inches unless noted UNIT SIZE MINIMUM MOUNTING PAD DIMENSIONS 18 24 23 x 42 30 36 48 24 x 50...

Страница 5: ...NS030000 124ANS036000 124ANS048000 Table 7 Dimensions SI ACs 124ANS018000 124ANS024000 124ANS030000 124ANS036000 124ANS048000 Table 8 Dimensions HPs 2 224ANS030000 224ANS036000 224ANS048000 Table 9 Di...

Страница 6: ...nstalling single or multiple units in an alcove roof well or partially enclosed area ensure there is adequate ventilation to prevent recirculation of discharge air SYSTEM REQUIREMENTS Clearances Allow...

Страница 7: ...g cable consists of three 3 wires Two wires are high voltage AC power and one is a ground wire Consult your local building codes and the NEC National Electrical Code or CEC Canadian Electrical Code fo...

Страница 8: ...stall indoor units near a direct source of heat such as direct sunlight or a heating appliance S Do not install units too close to humid conditions S Where an optimum air distribution is ensured S Whe...

Страница 9: ...TXV kit Flexible piping is recommended CAUTION Failure to follow the following caution may result in equipment damage or improper operation Insulate liquid and vapor pipes connecting to indoor and out...

Страница 10: ...to each suspension bolts making space for hanging the indoor unit S Hang the indoor unit to the suspension bolts between two nuts see Fig 18 S Screw the nuts to suspend the unit S Adjust level of the...

Страница 11: ...adient of 2 without obstruction see Fig 20 DO NOT install the drainpipe to an upward position It may cause water to flow back to the unit S Make a trap of at least 2 in 51 mm in depth to prevent unple...

Страница 12: ...y damage the compressor at start up When more than 80 ft 24 4 m of interconnecting tubing is used consult the Residential Long Line Application Guide for required accessories 3 Insulate both lines A m...

Страница 13: ...njury or death Before performing service or maintenance be sure indoor unit main power switch is turned OFF and indoor blower has stopped Lock out and tag switch with a suitable warning label Power Wi...

Страница 14: ...the unit side panel and connect to the control terminal strip using either Fig 28 for AC units or Fig 29 for Heat Pump units A150280 Fig 28 40MKCB F 24AHA4 or 124ANS Connecting diagram A150282 Fig 29...

Страница 15: ...0 208 230 3 253 197 71 9 3 1 2 12 8 20 48 50 83 1 13 7 1 45 18 6 30 36 60 460 3 506 414 38 5 6 0 6 7 6 15 48 60 41 6 2 0 8 8 6 15 Table 19 40MKCB F Electrical Data Indoor Unit Size BTU Hr V Ph Hz Volt...

Страница 16: ...r Live wire L1 Nullline L2 interface 24V interface CN 20 Network module interface CN 12 Vertical swing motor interface CN 13 horizontalswing motor interface CN 10 Display boardinterface CN 15 Compress...

Страница 17: ...LivewireL1 NulllineL2 interface 24V interface CN20 Networkmodule interface CN12 Ver ticals wingmotor interface CN13 horizontalswingmotor interface CN10 Disp layboardinterface CN15 Sign alinterface Y...

Страница 18: ...nect switch to the unit s control box Use copper wire only between the disconnect switch and unit 5 If any accessories are being installed refer to the individual accessory instructions for guidance o...

Страница 19: ...ect manifold gage charge hose to a charge port of the low side service valve see Fig 40 2 Connect charge hose to vacuum pump 3 Fully open the low side of manifold gage see Fig 41 4 Start vacuum pump 5...

Страница 20: ...t mode the unit will run in cooling and heating on heat pumps regardless if there is demand or not TEST OPERATION FOR UNDER CEILING CONSOLE Perform test operation after completing gas leak and electri...

Страница 21: ...down Procedure The system may be pumped down in order to make repairs on the low side without losing complete refrigerant charge 1 Attach pressure gage to suction service valve gage port 2 Front seat...

Страница 22: ...s NO Malfunction Running lamp Timer lamp Defrosting lamp Alarm lamp Display digital tube 1 Open or short circuit of T1 temperature sensor X X X E2 2 Open or short circuit of T2 temperature sensor X X...

Страница 23: ...w or too high Check temperature setting Outdoor unit fan faulty Replace outdoor fan Air or other non condensable gasses in the circuit Drain refrigerant evacuate and recharge CAUTION Do not vent refri...

Страница 24: ...P D 7310 W Morris St D Indianapolis IN 46231 Edition Date 07 15 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MKC...

Отзывы: