- 12 -
C-LOGIC 400-TC
EN
Period
Symbol
Default period time
Defaul period
temperature
Weekend
1
08:00
22ºC
2
23:00
15ºC
Note: If setting temperature is “00”, this time interval is shutdown.
Advanced setting (Suggestion: operated by technician)
Under power off state, press and hold “ ” Under power off state, press and
hold “
” in order to enter in the advanced setting menu. Each parameter can
be changed by pressing “ ” and ”
” keys and confirmed by pressing “SET”
key, progressing to the next parameter. The advanced settings in this menu are
indicated below:
No Symbol
Description
Parameter range
Factory
default
1
dIF
Temperature
hysteresis
0.5ºC – 4.5ºC
1.0ºC
2
SUH
Set upper
temperature
value
5ºC – 99ºC
1. 35ºC
3
SUL
Set lower
temperature
value
5ºC – 99ºC
2. 5ºC
4
AdJ
Room
temperature
adjust
(Calibration)
-5ºc – 5ºC
3. 0.0ºC
5
FrE
Anti-freezing
function
00: Anti-freezing function
shutdown
01: Anti-freezing function
enabled
00
6
LOC
Lock function
00: Lock disabled
01: Half lock
02: Full lock
00
7
FAC
Factory
default
08: Maintaining current
settings
00: Restore Factory default
08