15
Dosing Pump
The BWT Disinfecton is equipped with an internal dosing pump, which is governed by the controller, based
on the pulses from the water meter. Connect the supplied 6 mm clear, soft PVC hose, through the designated
hole in the plastic spill tray, to the fitting on the suction side of the pump.
Place the other end of the hose at the bottom of the Neuthox tank and install the supplied foot valve.
Dosing connector
The dosing connector has a 1/2 "external thread. The dosing connector contains a shortened internal check
valve. This means the tube can be seated in the middle of the pipe. It can be installed in all directions.
Water meter
To prevent overdosing during low water usage pulses from a water meter is recorded in the controller/HMI
and dosing stopped if water consumptions drops below specified values entered in the controller/HMI. The
2-lead cable from the water meter is connected directly to the terminals inside the cabinet. If the water meter
uses a transistor output be aware of polarity.
See the electrical diagram for more information.
Communication
A communication system can be connected to the BWT Disinfecton.
Ethernet Modbus
If the machine is equipped with an Ethernet card, communication via Modbus TCP/IP or Remote Access
(Unitronics freeware) is possible. Connect to the unit via the RJ45 plug on the side of the cabinet.
SMS communication
If the machine is equipped with a Modem for mobile phone messages. Insert
a SIM card into the modem
Neuthox production configurations
Содержание Disinfecton
Страница 1: ...1 BW T Disinfecton On site production of disinfection liquid Installation and Operating manual EN...
Страница 8: ...8 Type Key...
Страница 9: ...9 Product overview Electrical cabinet Hydraulic cabinet...
Страница 27: ...27 Spare part drawings...
Страница 28: ...28 PI diagram...
Страница 29: ...29 Arrangement drawing...
Страница 32: ...32 Declaration of Conformity...