42
EN
Firmly insert the flushing water hose into the flushing
water connection elbow (
9
).
Route the flushing water hose at an incline to the
sewage system connection (drain) and secure the
end with the fixing material supplied to prevent it
“flapping about” when under pressure.
Attach the overflow hose (18 x 24) to the overflow
(
10
). Secure it with cable ties and route it with an
incline of at least 10 cm to the sewage system
connection (drain).
A bypass is integrated into Multiblock X. The unit
can be installed in horizontal or vertical pipelines.
Follow the separate installation instructions for the
Multiblock; otherwise, warranty claims are void if
the unit becomes damaged.
Rinse out any dirt particles by opening the
handwheel on Multiblock X.
> 20 mm
6.1
Installation diagram
Strainer
Floor
sensor
Sewage
system
connec-
tion
Water
stop
9
10
Install the product as shown in the drawing. The
flushing water and overflow hoses must not be
connected or constricted at any point.
Attach the flushing water and overflow hoses to the
sewage system connection at least 20 mm above
the highest possible waste water level.