INSTALLATION AND PREPARATIONS FOR USE
!
Ventilation requirements
• For rooms with a volume of less than 5 m³ - permanent
ventilation of 100 cm² is required.
•
For rooms with a volume of between 5 m³ and 10 m³
a permanent ventilation of 50 cm² will be required
unless the room has a door which opens directly
in which case no permanent ventilation is
required.
•
For rooms with a volume greater than 10 m³ - no
permanent ventilation is required.
Pay attention: Regardless of room size, all rooms
containing the appliance must have direct access to the
outside air via an openable window or
to
the outside,
equivalent. The
room containing the cooker should have an air supply in
accordance with BS 5440: Part 2.
3
Installation
Customer Helpline
0345 257 7271
Important information for installation engineer