Installation | 5
Instruction Manual COBRA NC 1000 B WCV_EN_en
11 / 32
5.2.3 Cooling Water Connection
CWI
CWO
PHE
CWI
Cooling water inlet
CWO
Cooling water outlet
PHE
Plate heat exchanger
• Connect the cooling water connections (CWI / CWO) to the water supply.
Connection size:
– G1/2, ISO 228-1 (CWI / CWO)
• Make sure that the cooling water complies with the following requirements:
Supply capacity
l/min
15
Water pressure
bar
1 ... 6
Supply temperature
°C
+5 ... +30
Required pressure differential across sup-
ply and return
bar
≥
1
• To reduce the maintenance effort and ensure a long product lifetime we recom-
mend the following cooling water quality:
Hardness
mg/l (ppm) < 90
Properties
Clean & clear
PH value
7 ... 8
Particle size
µm
< 200
Chloride
mg/l
< 100
Electrical conductivity
µS/cm
≤
100
Free chloride
mg/l
< 0.3
Materials in contact with the cooling water Stainless steel
NOTE
Water hardness unit conversion.
1 mg/l (ppm) = 0.056 °dh (german degree) = 0.07 °e (english degree) = 0.1 °fH (french
degree)