3.061 PID inverted
The actual value source (parameter 3.060) is inverted
0
= disable
1
= enable
To be adapted to customer installation, usually for vacuum application you have to enable this
parameter
►
3.061 = 1
Please note that PID inverted (usually used in vacuum process):
The PID actual value can be inverted using parameter 3.061. The actual value is imported inversely,
i.e. 0 V … 10 V correspond internally to 100%…0%.