Input / Output Description | 7
Pump Control Instructions INVEOR VFD R5 COBRA_EN_en
33 | 44
4.052 AI2 maximum input (%)
Specifies the maximum value of the analogue inputs as a percentage of the range:
Example:
0 … 20 mA
►
0% … 100%
4 … 20 mA
►
20% … 100%
100
►
20 mA
►
100% = default value to be adapted to your process
4.053 AI2 dead time (%)
Dead time as percentage of the range of the analogue input:
0 = no dead time default value, to be adapted to your process
4.054 AI2 filter time (second)
Filter time of analogue inputs in seconds:
0.02 = default value to be adapted to your process
4.060 AI2 function
Function of analogue input 2:
0 = analogue input
4.063 AI2 physical unit
Selection of different physical values to be displayed:
4.063 =
0
%
4.063 =
1
bar
4.063 =
2
mbar
4.063 =
3
psi
4.063 =
4
Pa
4.063 =
5
m
3
/h
4.063 =
6
l/min
4.063 =
7
°C
4.063 =
8
°F
4.063 =
9
m
4.063 =
10
mm
4.064 AI2 physical unit minimum
Selection of the lower limit of a physical value to be displayed:
0 = default value to be adapted to your process
4.065 AI2 physical unit maximum
Selection of the upper limit of a physical value to be displayed:
100 = default value to be adapted to your process