Device Functions
System Manual 2CKA001473B9426
│19
Extension unit operation
– An additional operation for switching on/off using a push-button on the extension input 1C of
the presence detector.
– A manual change of the current switching state can be implemented. The return to
automatic mode and/or previously selected operation mode takes place after the room is
left plus the set switch-off delay.
– The lighting is also switched on in semi-automatic mode through the operation of this
extension.
Continuous ON
– The lighting is switched on. For devices with infrared remote control, the duration amounts
to 8 hours. For devices with Bluetooth function, the duration is freely selectable through the
smartphone app "Busch-Wächter
®
Remote control".
– For the activation of this function, a push-button is connected to channel 1 of the 6494
Extension unit connection. In the case of the DALI master, the "Continuous Light"
function must be activated by extension push-button.
– The return to automatic mode and/or previously selected operation mode is
implemented through one of the following possibilities:
■
Push-button/extension operation (directly connected to the extension input 1C of the
presence detector).
■
Simultaneous actuation of the push-buttons for "Continuous ON" and "Continuous
OFF".
■
By app.
■
Automatic after the expiration of the "Continuous ON" time.
– This function cannot be combined with the panel light.
Continuous OFF
– The lighting is continuously switched off. For devices with infrared remote control, the
duration amounts to 8 hours. For devices with Bluetooth function, the duration if freely
selectable through the smartphone app "Busch-Wächter
®
Remote control".
– The continuous light is operated using a separate switch connected through the 6494
Extension unit connection.
– For the activation of this function, a push-button is connected to channel 2 of the 6494
Extension unit connection. In the case of the DALI master, the "Continuous Light"
function must be activated by extension push-button.
– The return to automatic mode and/or previously selected operation mode is
implemented through one of the following possibilities:
■
Push-button/extension operation (directly connected to the extension input 1C of the
presence detector).
■
Simultaneous actuation of the push-buttons for "Continuous ON" and "Continuous
OFF".
■
By app.
■
Automatic after the expiration of the "Continuous OFF" time.
– This function cannot be combined with the panel light.