User Maintenance
A.
General Housekeeping (Continuous).
1. Keep boiler area clear and free of combustible
materials and obstructions to the free flow of
combustion and ventilation air to the boiler.
2. Do not store or use gasoline or other flammable
vapors or liquids in the vicinity of the boiler or any
other appliance.
3. Do not store or use sources of hydrocarbons in
the vicinity of the boiler. Sources of hydrocarbons
include bleaches, cleaners, chemicals, sprays, paint
removers, fabric softeners and refrigerants.
B.
Inspect Inlet Air and Vent System (Monthly).
Check
the following. If corrective action is required contact
qualified service agency.
1. Inlet air terminal and vent terminal must be free of
obstruction, undamaged, with screens securely in
place.
2. Inlet air terminal, vent terminal, and wall thimble (if
used) must be weather-tight.
3. Inlet air pipe and vent pipe must be full round
shape, showing no damage from impact or excessive
temperature.
4. Inlet air pipe and vent pipe must be supported at
minimum 5 foot intervals and must not sag.
5. All inlet pipe joints must be secure and airtight.
6. All vent pipe joints must be secure and watertight.
7. Condensate drain (if used) must have minimum 6
inch trap and allow condensate to flow freely. To
clean:
a. Disconnect condensate drain from drain fitting.
b. Flush condensate drain with water.
c. Securely fasten condensate drain to drain fitting,
providing gas-tight and water-tight seal.
C.
Inspect Pilot and Main Burner Flames (Monthly).
1. Remove jacket front panel.
2. View flames through combustion area enclosure.
See Figure 1.
3. Adjust thermostat to highest setting.
4. Check pilot flame. See Figure 4. The pilot produces
three (3) flames. The center flame should be steady,
medium hard blue enveloping
3
/
8
to ½ inch of
sensing probe. If flame is yellow and lazy, follow
instructions TO TURN OFF GAS TO APPLIANCE
(see Figure 2), and contact qualified service agency.
5. Check main burner flames. See Figure 5. Flame
should have clearly defined inner cone with no
yellow tipping. Orange-yellow streaks caused
by dust should not be confused with true yellow
tipping. If yellow flames are observed, follow
instructions TO TURN OFF GAS TO APPLIANCE
(see Figure 2), and contact qualified service agency.
6. Adjust thermostat to normal setting.
D.
Schedule Inspection by Qualified Service Agency
(Annual or at Beginning of Heating Season).
For
continued safe operation a qualified service agency
must provide a more detailed inspection of burners, heat
exchanger and vent system, and provide maintenance
as specified in Installation, Operating and Service
Instructions.
WARNING
Service on this boiler should be undertaken only by trained and skilled personnel from a qualified service
agency. Inspections should be performed at intervals specified in Installation, Operating and Service
Instructions and this manual. Maintain manuals in a legible condition.
Keep boiler area clear and free of combustible materials, gasoline and other flammable vapors and liquids.
Do not place any obstructions in boiler room that will hinder flow of combustion and ventilation air.
Содержание PVG Series
Страница 5: ... Figure 3 Sequence of Operation ...
Страница 7: ... Figure 4 Pilot Burner Figure 5 Main Burner Flame ...
Страница 13: ... Figure 3 Sequence of Operation ...
Страница 15: ... Figure 4 Pilot Burner Figure 5 Main Burner Flame ...