Aquastat IQ Option Card – Instruction Sheet 

 

Page 7 of 7

 

 

ORDERING INFORMATION 
 

Part Number 

Description 

102720-01 

Aquastat Limit Control IQ Option Card, 130-220 Deg F, Manual Reset for use with 
Option Control Panel, temperature sensor, well,  sensor clip, instructions, Unit Pack 

102717-01 

Aquastat Limit Control, IQ Option Card, 130-220 Deg F, 15 Deg F Adjustable 
Differential, Auto Reset, for use with Option Control Panel, temperature sensor, well,  sensor clip, 
instructions, Unit Pack 

102292-01 

Aquastat Limit Control IQ Option Card, 130-220 Deg F, Manual Reset for use with 
Option Control Panel, Less well, Less Sensor, Unit Pack 

102293-01 

Aquastat Limit Control, IQ Option Card, 130-220 Deg F, 15 Deg F Adjustable 
Differential, Auto Reset, for use with Option Control Panel, Less well, Less 
Sensor, Unit Pack 

 TROUBLSHOOTING

  

 
Aquastat IQ Option Card Error Codes 

The following errors are reportable via both EnviraCOM and the IQ Option Panel Display.  Errors will be displayed in 
view mode. 

 

Display 

Status 

Boiler / Control Action(s) 

Err

 

18 

Internal Failure 

 

Replace Control 

Err

 

119 

Sensor Failure

 

 

Temperature sensor or interface failure (open or short connection or 
increased connection resistance, dual sensor mismatch) or control 
hardware failure  

Err

 

25 

Lockout, manual reset 

required 

 

When a lockout occurs the boiler will shut down.  The boiler will not 
automatically restart once the temperature has decreased below the High 
Limit.  To Reset the control follow “Aquastat Reset Pushbutton procedure 
described above.

 

 

 

 

 
 

U.S. Boiler Company, Inc.

P.O. Box 3079

Lancaster, PA 17604

Содержание Aquastat IQ Option Card

Страница 1: ...safe levels Manual reset models require user intervention to reset a temperature condition after the temperature returns to safe levels SPECIFICATIONS Listings Approvals UL353 Limit Controls for both...

Страница 2: ...ed in accordance with all national and local codes and ordinances Risk of explosion Not for use in hazardous locations Serious injury or death could result When installations are complete check for co...

Страница 3: ...r Installation diagram above for details 8 Insert sensor clip to hold the sensor against the bottom of the well 9 Rout sensor wire and connect to Aquastat IQ Option Card 10 Turn power ON 11 Set High L...

Страница 4: ...the temperature of the controlled medium drops to the high limit setting minus differential the system should be operative again 2 Reset control to proper high limit setting Manual Reset Aquastat IQ...

Страница 5: ...ows the items that will be displayed in view mode View Mode Options HL High limit setting of Aquastat DF High limit differential of Aquastat St Sensor temperature of Aquastat err Error Followed By Err...

Страница 6: ...are pressed after five 5 minutes the display will automatically return to the view mode 5 Once in view mode press the key until bac option is displayed and press either Up or Down keys to return to th...

Страница 7: ...Deg F 15 Deg F Adjustable Differential Auto Reset for use with Option Control Panel Less well Less Sensor Unit Pack TROUBLSHOOTING Aquastat IQ Option Card Error Codes The following errors are reporta...

Отзывы: