Aquastat IQ Option Card – Instruction Sheet 

 

Page 3 of 7

 

INSTALLATION (continued) 

 

 

 

Sensor clip 

 

Sensor clip  

installed

 

Sensor Installation Diagrams 

 

Well and Sensor Installation 
1. 

Turn off all power and drain the boiler. 

2. 

Install sensor with well that was provided with the IQ Option Card.  When using an existing well ensure that the 
well specifications (Spud Size:1/2 inch NPT,  Insertion depth: 3 inches & Insulation: 1-1/2 inches) match the 
supplied well and will accommodate the supplied sensor clip.  

3. 

Prepare a properly sized and threaded tapping near the boiler supply water outlet.  Choose a location (or existing 
tappings) that allows the boiler water to circulate freely over the well. 

4. 

Sparingly coat the well threads with pipe dope. 

5. 

Install the well in the boiler tapping and tighten securely. 

6. 

Refill boiler and check for water leakage. 

7. 

Insert the sensor element into the well until it bottoms. See Sensor Installation diagram above for details 

8. 

Insert sensor clip to hold the sensor against the bottom of the well. 

9. 

Rout sensor wire and connect to Aquastat IQ Option Card 

10. 

Turn power ON. 

11. 

Set High Limit and High Limit Differential (see User Interface Section of this manual) 

IMPORTANT 
Best thermal response is obtained with a well that snugly fits the sensor. Insert the sensor until it rests against the 
bottom of the well. Use a well of correct length and install sensor clip.  If the well is not a snug fit on the sensor, use the 
heat-conductive compound, p/n 8056220, (Honeywell p/n 120650) 

 

IQ Option Card Installation 

1.  Turn off power to the boiler before installing 

the option card 

2.  Select an unoccupied IQ Option Panel slot 

and carefully insert pins on the IQ Option 
Panel header into the connector on the 
bottom of the option card.   

 

NOTE 

 

Use caution not to bend the pins. 

 
3.  Gently push the option card into the IQ 

Option Panel option slot until it locks into 
place. The IQ Option Panel will automatically 
recognize the option card and establish 
communication.   

 

 

 

Insert IQ Option Card into selected slot 

 

 

Содержание Aquastat IQ Option Card

Страница 1: ...safe levels Manual reset models require user intervention to reset a temperature condition after the temperature returns to safe levels SPECIFICATIONS Listings Approvals UL353 Limit Controls for both...

Страница 2: ...ed in accordance with all national and local codes and ordinances Risk of explosion Not for use in hazardous locations Serious injury or death could result When installations are complete check for co...

Страница 3: ...r Installation diagram above for details 8 Insert sensor clip to hold the sensor against the bottom of the well 9 Rout sensor wire and connect to Aquastat IQ Option Card 10 Turn power ON 11 Set High L...

Страница 4: ...the temperature of the controlled medium drops to the high limit setting minus differential the system should be operative again 2 Reset control to proper high limit setting Manual Reset Aquastat IQ...

Страница 5: ...ows the items that will be displayed in view mode View Mode Options HL High limit setting of Aquastat DF High limit differential of Aquastat St Sensor temperature of Aquastat err Error Followed By Err...

Страница 6: ...are pressed after five 5 minutes the display will automatically return to the view mode 5 Once in view mode press the key until bac option is displayed and press either Up or Down keys to return to th...

Страница 7: ...Deg F 15 Deg F Adjustable Differential Auto Reset for use with Option Control Panel Less well Less Sensor Unit Pack TROUBLSHOOTING Aquastat IQ Option Card Error Codes The following errors are reporta...

Отзывы: