Aquastat IQ Option Card – Instruction Sheet 

 

Page 4 of 7

 

INSTALLATION (continued) 

 

Checkout 

Check to make certain that the Aquastat IQ Option Card has been installed and adjusted to the proper settings.  Put 
the system into operation and observe the action of the device through several cycles to make certain that it provides 
proper control of the system as described in the Operations section. Further adjustments can be made to meet more 
exact comfort requirements. 
 

Operation 

Automatic Reset Aquastat IQ Option Cards: 

1. 

When checking out the system, adjust the control point low enough so the temperature of the controlled medium 
reaches the high limit setting and the burner shuts off. When the temperature of the controlled medium drops to the 
high limit setting minus differential the system should be operative again. 

 

2. 

Reset control to proper high limit setting.

  

 

 
Manual Reset Aquastat IQ Option Cards: 

1. 

When checking out the system, adjust the control point low enough so the temperature of the controlled medium 
reaches the high limit setting, the burner shuts off, and the Aquastat Controller “locks out”. When the temperature 
of the controlled medium drops to the high limit setting minus differential, activate the manual reset button (refer to 
“How To Reset The Aquastat” below for reset procedure) and the system should be operative again. 

 

2. 

Reset control to proper high limit setting.

  

 

USER INTERFACE 

Aquastat IQ Option Card Features  

 

LED Description 

 

Flashing 

Red

 

 

High Temperature, Lockout and manual 
reset required or fault indicator 

Green TX 

 

Enviracom® communication indicator 

 

Содержание Aquastat IQ Option Card

Страница 1: ...safe levels Manual reset models require user intervention to reset a temperature condition after the temperature returns to safe levels SPECIFICATIONS Listings Approvals UL353 Limit Controls for both...

Страница 2: ...ed in accordance with all national and local codes and ordinances Risk of explosion Not for use in hazardous locations Serious injury or death could result When installations are complete check for co...

Страница 3: ...r Installation diagram above for details 8 Insert sensor clip to hold the sensor against the bottom of the well 9 Rout sensor wire and connect to Aquastat IQ Option Card 10 Turn power ON 11 Set High L...

Страница 4: ...the temperature of the controlled medium drops to the high limit setting minus differential the system should be operative again 2 Reset control to proper high limit setting Manual Reset Aquastat IQ...

Страница 5: ...ows the items that will be displayed in view mode View Mode Options HL High limit setting of Aquastat DF High limit differential of Aquastat St Sensor temperature of Aquastat err Error Followed By Err...

Страница 6: ...are pressed after five 5 minutes the display will automatically return to the view mode 5 Once in view mode press the key until bac option is displayed and press either Up or Down keys to return to th...

Страница 7: ...Deg F 15 Deg F Adjustable Differential Auto Reset for use with Option Control Panel Less well Less Sensor Unit Pack TROUBLSHOOTING Aquastat IQ Option Card Error Codes The following errors are reporta...

Отзывы: