Burnham Aquastat IQ Option Card Скачать руководство пользователя страница 1

 
 
 
Aquastat®

 

IQ Option Card, p/n 102720-01, 102717-01

 

 
 

Instruction Sheet 

 

APPLICATION 

The Aquastat IQ Option Card provides electronic 
temperature sensing in a UL limit-rated control with a 
single sensing probe. The Aquastat IQ Option Card 
replaces auxiliary high limit Aquastats such as 

 

L4006A, L4008A, L4006E and L4008E.   
 
This product may be applied to either gas or oil fired 
steam or hot water boilers equipped with the IQ 
Control System.  The Aquastat  IQ Option card may 
be simply “plugged in” to the IQ Option Panel and 
only requires sensor and well installation to become 
operational.  
  

GENERAL 

The Aquastat IQ Option Cards are available in 
automatic or manual reset models.  Automatic reset 
versions automatically reset when temperature return 
to safe levels.  Manual reset models require user 
intervention to reset a temperature condition after the 
temperature returns to safe levels.    

 

SPECIFICATIONS

  

Listings/Approvals 

 

UL353 Limit Controls for both US (UL) and 
Canada (CUL)—Component Recognized 

 

UL 1998 Software Safety Standards as a Class 2 
device.  

 

Add a  Manual Reset Aquastat IQ Option Card, 
p/n 102720-01, to the factory mounted 
temperature control to be Fully compliant with 

CSD-1 requirements

 for temperature controls in 

the US and Canada 

 

 

Dimensions: 

4.5 in. x 1.5 in. (fits onto IQ Option Panel) 

Operating temperature: 

-4°F to 150°F 

Shipping and Storage: 

-40°F to 175°F 

Humidity 

0 to 95% R.H. Non-condensing 

Input ratings: 

24 VAC 60 Hz 

Reset: 

Automatic or manual reset modes  

Sensor: 

Dual Sensor, Limit Rated, p/n102295-01 

 

(Honeywell p/n 50001464-004) 

 

with sensor clip 102422-01 

Well: 

p/n 

80160456, (Honeywell p/n 123869A), 

 

Spud Size:1/2 inch NPT  

 

Insertion: 3 inches 

 

Insulation: 1-1/2 inches

 

 

102715-01-6/09 

Содержание Aquastat IQ Option Card

Страница 1: ...safe levels Manual reset models require user intervention to reset a temperature condition after the temperature returns to safe levels SPECIFICATIONS Listings Approvals UL353 Limit Controls for both...

Страница 2: ...ed in accordance with all national and local codes and ordinances Risk of explosion Not for use in hazardous locations Serious injury or death could result When installations are complete check for co...

Страница 3: ...r Installation diagram above for details 8 Insert sensor clip to hold the sensor against the bottom of the well 9 Rout sensor wire and connect to Aquastat IQ Option Card 10 Turn power ON 11 Set High L...

Страница 4: ...the temperature of the controlled medium drops to the high limit setting minus differential the system should be operative again 2 Reset control to proper high limit setting Manual Reset Aquastat IQ...

Страница 5: ...ows the items that will be displayed in view mode View Mode Options HL High limit setting of Aquastat DF High limit differential of Aquastat St Sensor temperature of Aquastat err Error Followed By Err...

Страница 6: ...are pressed after five 5 minutes the display will automatically return to the view mode 5 Once in view mode press the key until bac option is displayed and press either Up or Down keys to return to th...

Страница 7: ...Deg F 15 Deg F Adjustable Differential Auto Reset for use with Option Control Panel Less well Less Sensor Unit Pack TROUBLSHOOTING Aquastat IQ Option Card Error Codes The following errors are reporta...

Отзывы: