background image

11. 

Additional Servicing and Technical Information 

 

1.

 

Flue Gas Analysers – Installation & Servicing Facts 

 

 

Please read this sheet even if you have fitted our fires before.  
 

 

Please leave this sheet with the customer as reference for future servicing of the appliance.  

 

 

Please  explain  to  the  customer  how  the  fire  works  and  the  details  and  facts  listed  on  this 
sheet, particularly what the catalyst does and doesn’t do.  
 

 

If you have any doubts about the test procedure please visit our website or call our technical 
help line 

 

Testing – Points to note…  
 

 

Before testing ensure that the room size is correct for the heat output of the fire. 30cu³ for 
2.5kw output, 40cu³ for 3.5kw and 50cu³ for 4.5kw.  

 

 

In all installations regardless of room size there must be an air vent positioned at least one 
metre from the fire at either high or low level through an outside wall providing 100cm² of 
free air. (For the Republic of Ireland 2 vents of not less than 60cm² must be provided at high 
and low level, with minimum vertical separation of 1.6m). 

 

 

The  analyser  used  must  be  manufactured  to  BS7967  and  the  test  must  be  carried  out  in 
accordance with BS5871 Pt 4 

 

 

The catalytic converter needs heat to work, therefore before you start testing; the fire must 
have been lit and burning on full for at least 15 mins.  

 
There are two tests to carry out. A Co / CO² ratio test and a room centre CO test.  
 

1.

 

The first test is the CO / CO² ratio test and should be carried out at the fire exhaust vent, do 
not stick the probe of the analyser in through the grill but move the probe back and forth 1 
inch  in  front  of  the  outlet  grill.  (We  use  a  piece  of  perforated  8mm  pipe  attached  to  the 
analyser  with  flexible  rubber  tube).  You  should  record  a  ratio  of  no  more  than  0.002  % 
(20ppm CO to 1%  Co²). It is advisable to  have a high sample of CO as this will improve the 
test 

 

2.

 

The  second test is the room centre CO test. You should stand in  the room centre  with  the 
probe  at  waist  height  and  read  the  level  of  CO;  this  should  be  no  more  than  9ppm  over 
ambient peak. Please record these readings on the customers guarantee card.  

 
Our Flueless fires also contain the following safety devices (an ODS (Oxygen Depletion Sensor) and 
FSD (Flame Supervision Device). Point out to the customer that unfortunately these are not found 
on all gas hobs; which are also flueless devices)

 

 
 
 
 

Содержание G4220 - 9

Страница 1: ...ances Ltd Lands End Way Oakham Rutland LE15 6RB Telephone 44 0 1572 756956 Fax 44 0 1572 724390 e mail info burley co uk web www burley co uk G4221InstUser G20 31 Issue MARCH 09 v 4 TO OBTAIN YOUR FIR...

Страница 2: ...egory I2H I3P Supply Pressure 20mBar 37mBar Inlet Pressure 20mBar 37mBar Heat Input Net High 2 5kW 2 5kW 180g h Low 1 5kW 1 5kW 107g h Inlet Connection 8mm Compression 8mm Compression Injector Elbow 3...

Страница 3: ...on the appliance is to prevent risk of fire or injury from burns and no part of it may be permanently removed It does not give full protection for young children the elderly or infirm Parts of the ap...

Страница 4: ...n a floor can lead to discolouration and or drying out When a hearth is used the top surface can be wood but be aware that heat can discolour certain finishes over a period of time and can dry out poo...

Страница 5: ...e met then the appliance should not be installed Consideration should be given to the requirements of other appliances working in the same room space If other flueless appliances such as cookers are i...

Страница 6: ...he coal sits with the 4 coal shapes uppermost and coal profile facing you The feet on the front coal locate between the burner and tags in the burner tray Always secure the door closed after laying th...

Страница 7: ...The left hand one coloured red controls On Off and High Low flame The right hand one coloured black is the comfort level thermostat which turns the fire to pilot position once the desired temperature...

Страница 8: ...ommencing any servicing ensure that the gas is isolated and the appliance is cool Cleaning The casing should be wiped with a cloth dampened in soapy water The glass may be cleaned with any non abrasiv...

Страница 9: ...for their use Using unapproved accessories could prove hazardous and will invalidate the warranty User Instructions Read the instructions before using this appliance This appliance requires installat...

Страница 10: ...ry out the lighting procedure to re ignite Cleaning the fuel effect Switch the appliance OFF and allow to cool before commencing The fuels can be accessed by opening the hinged door on the appliance w...

Страница 11: ...ured to BS7967 and the test must be carried out in accordance with BS5871 Pt 4 The catalytic converter needs heat to work therefore before you start testing the fire must have been lit and burning on...

Страница 12: ...ult the relevant manufacturer Only use replacement catalyst supplied by Burley If you or the customer detects any odours from the fire please remember that the catalytic convertor is not an air filter...

Страница 13: ...ant to take a gas rate test over a reasonable period of time so that the capacity of the meter is used On low Input appliances such as our flueless this is even more critical because uncertainties can...

Страница 14: ...first year as with all gas products every gas appliances must be serviced every year The appliance has not been subject to misuse accident or repaired or fitted by anyone other than a Gas Safe regist...

Отзывы: