![Bürkert 8791 Скачать руководство пользователя страница 32](http://html.mh-extra.com/html/burkert/8791/8791_operating-instructions-manual_2832023032.webp)
32
Functions
funcTiOns
10.
The positioner type 8691 has different basic and additional functions which can be configured and parameterized
via the DIP switches or the communications software.
Basic functions
10.1.
The following basic functions can be activated via the DIP switches (
CUTOFF
and
CHARACT
) or changed
(
DIR.CMD
).
function
description
dip switches Off
On
DIR.CMD
Effective sense of direction
between input signal and set-point
position
1
Ascending
Descending
CUTOFF
Sealing function for position
controller
2
Sealing function off
Sealing function on
CHARACT
Selection of the transfer charac-
teristic between input signal and
stroke (correction characteristic)
3
Linear characteristic Correction
characteristic
Basic functions of DIP switches
Table 12:
The following basic function can be changed via the communications software only.
function
description
factory settings
INPUT
Input of the standard signal input
for the set-point default
4 to 20 mA
Basic function of communications software
Table 13:
The
INPUT
,
CUTOFF
and
CHARACT
functions can be parameterized via the communications software.
The instructions for the communications software describe in detail the individual menu options, as well as
parameterization and configuration.
These instructions can be found on the internet at
Documentation Type 8791
and
are also available on CD which can be ordered by quoting identification number 804625.
english
Type 8791