Technical Data
factory settings of the positioner
8.2.
functions can be activated via dip switches
8.2.1.
function
parameter
value
CUTOFF
Sealing function below
Sealing function above
2 %
98 %
CHARACT
Select characteristic
FREE
DIR.CMD
Effective direction set-point value
increasing
Factory settings; Functions can be activated via DIP switches
Table 3:
functions can be activated via communications software
8.2.2.
function
parameter
value
INPUT
Set-point value input
4 ... 20 mA
DIR.ACTUATOR
Effective direction actual value
increasing
SPLITRANGE
Signal split range below
Signal split range above
0 %
100 %
X.LIMIT
Function deactivated
Stroke limit below
Stroke limit above
0 %
100 %
X.TIME
Function deactivated
Actuating time Open
Actuating time Closed
(1 s) values determined by
X.TUNE
(1 s) values determined by
X.TUNE
After implementation of RESET: 1 s
X.CONTROL
Dead band
Open amplification factor
Close amplification factor
1,0 %
(1) values determined by
X.TUNE
(1) values determined by
X.TUNE
After implementation of RESET: 1
SAFEPOSITION
Safety position
0 %
SIGNAL ERROR
Sensor break detection set-point value
OFF
BINARY INPUT
Function active
Binary input function
Operating principle of binary input
Safety position
Normally open contact
OUTPUT
Function active
Norm signal output: Parameter
Norm signal output: Type
Position
4 ... 20 mA
Factory settings; Functions can be activated via communications software
Table 4: