Maintenanceandtroubleshooting
red
leD
current
output
transistor
output
icon message
displayed in the
info menu
possible cause
recommended action
ON
22 mA
depending
on
thresholds
ERR
+
"S PT Missing"
The connection to the
Pt1000 probe is lost.
The temperature
is displayed in the
Process level with
“+++++°C/°F”.
→
Check that the nut
between the sensor
holder and the elec-
tronic module is cor-
rectly screwed.
→
Send the device back
to Bürkert
ON
22 mA
depending
on
thresholds
ERR
+
"S PT
Regulation"
The fluid temperature
is not being correctly
measured.
The process is stopped.
→
Switch the power
supply off then on
again.
→
if the error persists,
return the device to
Bürkert.
ON
22 mA
depending
on
thresholds
ERR
+
"TR EE Fact
Read"
Parameter reading error.
→
Switch the power
supply off then on
again.
→
if the error persists,
set the device back
to the default settings
(chpt. 9.11.4).
→
if the error persists,
return the device to
Bürkert.
"TR EE User
Read"
ON
22 mA
depending
on
thresholds
ERR
+
"TR COM
Measure"
The acquisition/
conversion module of
the process values is
faulty.
The process is stopped.
→
Switch the power
supply off then on
again.
→
if the error persists,
return the device to
Bürkert.
ON
22 mA
depending
on
thresholds
ERR
+
"TR EE
UserWrite"
Parameter saving error.
→
Switch the power
supply off then on
again.
→
Save the settings
again.
→
if the error persists,
set the device back
to the default settings
(chpt. 9.11.4).
→
if the error persists,
return the device to
Bürkert.