![Bürkert 8222 ELEMENT NEUTRINO Скачать руководство пользователя страница 59](http://html1.mh-extra.com/html/burkert/8222-element-neutrino/8222-element-neutrino_operating-instructions-manual_2832001059.webp)
59
Adjustmentandstart-up
When a “warning” or “error” event is generated by the device:
→
go into the “Info” menu to read the cause of the event generation.
→
and/or go into the “Sensor” function of the Diagnostic menu to read the measured temperature value.
→
then check whether the built-in Pt1000 is working correctly by measuring a fluid with a known temperature. If
the Pt1000 is faulty, return the device to Bürkert.
→
if the Pt1000 is not the cause of the problem, check the process.
• The "warning" event may also be associated with one or other or both transistor outputs. See
chpt. 9.11.10, function "Output.TR1" or "Output.TR2".
• The "error" event may also be associated with one or other or both current outputs. See chpt. 9.11.9,
function "Output.AC1" or "Output.AC2".
• See also chpt. 10.3 Solving a problem.
ACTIVATE
: choose whether or not to activate monitoring of the fluid temperature.
TEMPERATURE
: read the fluid temperature measured in real time through the built-in Pt1000.
WARN HI
: enter the fluid temperature value above which a “warning” event is generated.
WARN LO
: enter the fluid temperature value below which a “warning” event is generated.
ERR HI
: enter the fluid temperature value above which an “error” event is generated.
ERR LO
: enter the fluid temperature value below which an „error“ event is generated.
9.14 Knowing the Test menu
9.14.1 Modifying the Test menu access code
See chpt. 9.9 to access the Test menu.
System
Code
0***
Confirm code
0***
Test
Enter the new code
Confirm the new code
If the default code (0000) is entered, the code will not be requested to access the menu.