24 - 2702
C
ommissioning
english
eleCtRICal ConneCtIon - teRMInal foR Cable bUshIng
(sIde
CONTROL
tYPe 1067)
attentIon!
To ensure electromagnetic compatibility (EMC resistance), the interior M4 threading of the
armature must be connected to ground with the shortest possible cable.
Signal input
- either for target position
(operation as positional control)
-
or for process target value
(operation as process controller)
- input for actual process value
Binary input
Contact
Output
(Option)
Suppply voltage
Jumper position
Input
U1 (Unit signal
0 ... 10 V)
Input impedance
200 k
W
Input
I1
(Unit signal
0/4 ... 20 mA)
Input impedance
> 175
W
Input
I2
(Unit signal
4 ... 20 mA)
Input impedance
> 175
W
Pin assignment
M4-internal thread
Содержание 2702