20
Technical data
Type 8098 FLOWave L
6
TECHNICAL DATA
6.1
Operating conditions
Ambient temperature
Depends on the liquid temperature (see
• Device variant with
two M20x1.5 cable
glands and one 5-pin M12
connector
•
–10 °C...+70 °C, if the liquid temperature is –10 °C...+80 °C (see Fig. 9)
• See
Fig. 9, if the liquid temperature is higher than +80 °C
•
Device variant with two 4-pin
M12 female connectors and
one 5-pin M12 connector
(Ethernet device variant)
•
–10 °C...+55 °C (see Fig. 10)
Air humidity
< 85 %, non condensing
Height above see level
max. 2000 m
Operating conditions
Continuous operation
Equipment mobility
Fixed device
Use
Indoor and outdoor
▶
Protect the device against electromagnetic interference, ultraviolet rays
and, when installed outdoors, against the effects of climatic conditions.
Installation category
Category I according to UL/EN 61010-1
Degree of pollution
Degree 2 according to UL/EN 61010-1
IP-Code according to IEC/
EN 60529
IP65
1)
, IP67
1)
if the following conditions are observed:
• The device must be wired.
• The cable glands must be tightened.
• The covers must be screwed tight.
• Unused cable glands must be sealed with the blind plugs provided.
The blind plugs are mounted upon delivery of the device.
• Unused M12 connectors must be protected by a screwed plug.
Protection type according to
NEMA250
1)
4X if the following conditions are observed:
• The device must be wired.
• The cable glands must be tightened.
• The covers must be screwed tight.
• Unused cable glands must be sealed with the blind plugs provided.
The blind plugs are mounted upon delivery of the device.
• Unused M12 connectors must be protected by a screwed plug.
1)
not evaluated by UL; only IP64 is evaluated by the ATEX / IECEx notified/certification body.
→
For the special operating conditions of devices with ATEX / IECEx certification, refer to the ATEX / IECEx
supplement for the device. The supplement is available at country.burkert.com.