61
Electrical installation
Type 8098 FLOWave L
8.17
Specifications of the cables and conductors for the
4-pin M12 female connectors
Table 18:
Specifications of the cables and conductors for the 4-pin M12 female connectors
Specification of the cables and conductors
Recommended value
Electromagnetic protection (EMC)
Shielded conductor with minimum STP
Minimum category
CAT-5
Maximum length
100 m
Maximum operating temperature
80 °C or higher
8.18
Connecting the device to an Ethernet network
(device variant with two 4-pin M12 female
connectors - Ethernet device variant)
The two 4-pin M12 female connectors (D-coding) are used to connect the device to an Ethernet network.
Risk of damage to the device if any M12 connector is unused.
• Put a screwed plug on all the unused M12 connectors. Screw the plug to the 4-pin M12 female
connector to a torque of 1.3 Nm (0.96 ft·lbf).
If a device with two 4-pin M12 female connectors (Ethernet device variant) is connected to an Eth
-
ernet network, you must connect it to a büS / CANopen network for the configuration of the device
with the software Bürkert Communicator.
If a device is connected to an Ethernet network, the measured process values are transmitted via the Eth
-
ernet network.
Each 4-pin M12 female connector (D-coding) has the same pin assignment: See Fig. 36
.
1
2
3
4
•
Pin 1: Tr
•
Pin 2: R
•
Pin 3: Transmit –
•
Pin 4: Receive –
Fig. 36:
Pin assignment of the 4-pin M12 female connector
→
Loosen the screwed plug of the 4-pin M12 female connector and store the screwed plug in a safe and
clean place.