69
Electrical installation without fieldbus communication
13.3.5
Terminal layout for operating voltage
Terminal Assignment
External circuit/signal level
+24 V
Operating v
+24 V
GND
24 V DC ±25%
max. residual ripple 10%
GND
Operating voltage GND
Table 34:
Terminal layout operating voltage
13.3.6
Terminal assignment for external position sensor
(only for remote variant)
Terminal Assignment
Device end
External circuit/signal level
S +
Sensor
S +
+
Remote
sensor
Type 8798
23)
S –
Sensor supply –
S –
–
A
Serial interface, A-line
A
A-line
B
Serial interface; B-line
B
B-line
23) For assignment of wire colour see “Table 36”.
Table 35:
Terminal assignment, external position sensor
Positioner
terminal
Wire colour
Remote sensor with cable type 1
Wire colour
Remote sensor with cable type 2
S +
brown
brown
S –
white
black
A
green
red
B
yellow
orange
Table 36:
Assignment of wire colour on the remote sensor
Type 8791, REV.2
english