
english
10 - 1094
english
Settings for DIP switches S 1-1 through S 1-5 and S 1-8: see 4.2.2
4.2.3 DIP switches settings with Type 1094 PHR
(Order no. 154463)
S 1-6
S1-7
PWM-Frequency
OFF
OFF
1000 Hz
ON
OFF
1250 Hz
OFF
ON
3000 Hz
ON
ON
6000 Hz
4.2.4 Setting the DIP switches for the 1094 PMR Type
Setting at delivery
PWM-Frequency
DIP-Switch
low
medium
S 1
OFF
ON
suitable for valve
type
2834, 2836, 6023, 6024,
6223 (DN 20)
2832, 2834, 6022, 6023,
6223 (DN 10, 13)
Zero-point switch-off
DIP-Switch
aktivated
de-aktivated
S 2
OFF
ON
Generally, each of the four combinations of dip-switch settings can be used.
With the lowest frequency, the lowest hysteresis is obtained, the PWM
signal, however, is still slightly audible, whereas with the highest frequencies
practically no noise is perceptible.The sensisitivity and hence the excellent
functionality in closed-loop control applications, however, is guaranteed with
all the four frequency settings.
Содержание 1094 Series
Страница 20: ...english 18 1094 english NOTES ...
Страница 38: ...d e u t s c h 36 1094 deutsch NOTIZEN ...
Страница 56: ...54 1094 français français ...
Страница 57: ......
Страница 62: ......
Страница 63: ......
Страница 64: ...The smart choice of Fluid Control Systems www buerkert com ...