Humidity function
Depending on the difference between the set humidity and room humidity sensed by sensor,
the following humidity controller functions :
(1) room humidity display range : 25%RH ˜ 90%RH
1) room humidity less then 25%RH : LO% display
2) room humidity more then 90%RH : HI% display
(2) room humidity control range : 30%RH ˜ 80%RH(default : 55%RH) ☜ CPA
(3) desensitized belt(DB) humidity(DB, controlled output does not respond to the slight
fluctuation in room humidity) : 1%RH ˜ 10%RH(default : 1%RH) ☜ DB
(4) proportional range or step control range : 2%RH ˜ 20%RH(default : 2%RH) ☜ PB
(5) step humidity control range : 2%RH ˜ 20%RH(default : 5%RH) ☜ STEP
(6) example for the control depending on the humidity setting
[ in case of CPA = 55%, PB = 5%, DB = 2% ]
- in case of compressor use 1 or 2 unit(2cycle)
- in case of compressor use 3 unit(3cycle)
- in case of AHU unit