INSTALLATION 

 

The  Installation  of  KlassKeeper  units  and  accessories  must  be  in  accordance  with  all  local  codes  and 
regulations of all relevant governing authorities having jurisdiction. The following installation procedures 
are recommended by the Manufacturer.  
 

It is the responsibility of the installing contractor to comply with all applicable codes and regulations.  
It  is  the  responsibility  of  the  installing  contractor  to  ensure  adequate  service  clearance  for  regular 
maintenance  or  for  repair  in  place,  is  exercised.  The  installing  contractor  will  be  responsible  for 
removing the unit if it is not repairable in place. 

 
 

Delivery and General Installation Checklist 

 

The information below details the correct installation procedure for a KlassKeeper unit. Please read this 
document in its entirety prior to proceeding with unit installation. 
Specific site conditions may warrant variations in locations and dimensions. 
 

1.

 

Remove packaging and inspect the unit. Check for shipping damage or material shortage; file a 
freight claim and notify your sales representative if damage or deficiency is found. 

2.

 

Verify the correct model and voltage as indicated by the model number. 

3.

 

Verify the installation location of the unit. 

4.

 

Verify that the power supply complies with the nameplate specification. 

5.

 

Connect properly sized and protected power supply wiring to the disconnect in the cabinet.  

6.

 

Install proper grounding wires to an earth ground on the cabinet as well as the receptacle. 

 
 

Location 

 
Locate the unit in an indoor area. The indoor air temperature surrounding and being supplied to the unit 
must, at all times, be above 45F (7C). Do not locate the unit in areas subject to freezing. 
 
 

Cabinet Placement 

 

1.

 

Ensure that there is sufficient clearance in front of the unit to allow the swinging access door to 
open freely. A minimum of 5 feet shall be left unoccupied in front of the unit at the same width 
as the unit.  

2.

 

Plenum (when ordered) is factory assembled and shipped loose for field installation by others.  
Plenum is mounted on the cabinet’s top. 
 
 
 
 
 
 
 

Содержание KlassKeeper KKV024

Страница 1: ...Last Revised April 2020 Installation Operation Maintenance Manual KlassKeeper Heat Pump KlassKeeper Models KKV024 KKV048...

Страница 2: ...rant Charge 5 Unit Clearances 5 INSTALLATION 6 Delivery and General Installation Checklist 6 Location 6 Cabinet Placement 6 Dry Walling when required 7 Piping 7 Wiring 8 OPERATION 9 Inputs Outputs 9 O...

Страница 3: ...st Revised April 2020 Installation Operation and Maintenance Manual is Subject to Change without Notice MAINTENANCE 17 Inspect Filters 17 Check Fan motors annually 17 Visual Inspection 17 Amperage Che...

Страница 4: ...cting the unit to conditions of this nature may result in significantly reduced performance reliability and operational life The unit is intended for interior use only and should be stored indoors at...

Страница 5: ...Keeper Installation Operation and Maintenance Manual 4 Copyright 2013 CGC Group Inc Last Revised April 2020 Installation Operation and Maintenance Manual is Subject to Change without Notice Unit Dimen...

Страница 6: ...Charge oz 40 45 50 60 Consult factory Unit Clearances Clearances for the KlassKeeper units shall be provided such that the access panel swinging door opens and closes without obstruction to allow ser...

Страница 7: ...unit installation Specific site conditions may warrant variations in locations and dimensions 1 Remove packaging and inspect the unit Check for shipping damage or material shortage file a freight cla...

Страница 8: ...all screw must not be longer than the drywall thickness plus a maximum 3 8 Ensure drywall is not obstructing the swinging access door Piping CAUTION Piping must comply with all applicable codes and re...

Страница 9: ...bject to Change without Notice Wiring 1 Connect the wire harnesses between the chassis ERV and cabinet as per the below diagram 2 Connect the power plug to the receptacle in the cabinet Wire Harness T...

Страница 10: ...dry contacts on the third party controller or thermostat Analog Inputs TH1 Discharge Air Temperature TA TH2 Refrigerant Temperature TR TH3 Leaving Water Temperature TW TH4 Exhaust Entering Air Tempera...

Страница 11: ...will also be opened whenever there is a cool call in place To bring on the second stage of cooling contact DI3 on the unit controller must be closed through a dry contact on the unit mounted third pa...

Страница 12: ...ED Flashcode The Flex controller has a multi colored Alarm LED that is used to communicate the previous alarm if any through the use of flashcodes If there have been no alarms this LED will be green I...

Страница 13: ...ompressor has been running for three minutes a low pressure alarm will be activated the compressorwill be turned off the general alarm contact K7 will be energized a flashcode of 5 will be displayed a...

Страница 14: ...ovides information about the unit s operation The first button on the left allows the user to scroll through three separate screens Screen 1 This screen provides information on the alarm status of the...

Страница 15: ...m Central heat injection and rejection equipment is automatically controlled via a CGC control panel or equivalent to provide the required loop water temperature for correct KlassKeeper Bulldog Heat P...

Страница 16: ...speed the unit must be placed into cool mode Clean Unit Filters Check to ensure the unit filters are clean each KlassKeeper unit is equipped with three filters a pleated supply air filter and a wire f...

Страница 17: ...system problems may cause less than optimum operation In the event that the qualified commissioning agents suspect there is an operational problem with the heat pump they need to inform the factory im...

Страница 18: ...esh air filter unscrew the corresponding access panel on the left of the cabinet and slide the filter out Slide a new filter into place make certain the arrow on the filter is pointing in the directio...

Страница 19: ...t is reset or power is disconnected for 20 seconds NOTE If the heat pump must be reset more than twice check the unit for a dirty air filter abnormal entering water temperature inadequate water flow d...

Отзывы: