background image

KlassKeeper – Installation, Operation, and Maintenance Manual 

14 

 

 

© Copyright 2013 CGC Group Inc.        

                                                     

Last Revised April 2020                                                                          Installation, Operation, and Maintenance Manual is Subject to Change without Notice.                                                                   

 

COMMISSION & STARTUP 

CAUTION: 
 
To avoid fouled machinery, extensive unit clean up and void warranty, do not operate units without 
filters in place or use as a temporary heat source during construction.   

 
The  Bulldog  KlassKeeper  Heat  Pump  provides  year  round  cooling  and  heating  as  controlled  by  unit 
thermostat or by a direct digital controller. 
 
It provides cooling using a water-cooled refrigeration circuit and provides heating using a hydronic coil. 
The compressor operates during cooling operation only and does not operate during heating operation 
thereby providing quieter operating sound levels and energy cost savings. The heat recovery module adds 
additional energy savings by transferring energy from the exhaust air to the supply air stream. 
 
Central heat injection and  rejection equipment is automatically controlled via a CGC control panel (or 
equivalent) to provide the required loop water temperature for correct KlassKeeper Bulldog Heat Pump 
units operation. 

 

System Flushing 

 

Proper system cleaning and flushing is an important aspect of the commissioning and start up procedure 
for KlassKeeper Units. Ensure the system has been flushed properly. This prevents fouling of the unit heat 
exchangers.  
 
NOTE: Hydronic coils are not 100% drainable.    
 

System Fluid 

 

Ensure that system water temperature is within an acceptable range to facilitate start-up (80-120F) for 
cooling and (100F – 140F) for heating 
 

System Water pH 

 

System water should have a neutral pH balance of approximately 7.5, which will extend the life of the 
hoses, heat exchangers, and other water side accessories. 
 

Water Flow Rate 

 

Open all isolation valves to the unit. Ensure that the entering and leaving fluid temperatures of the unit 
in operation are acceptable. Typically there is an 8-15⁰F (4.4-8.3⁰C) drop in heating and 10-15⁰F (5.5-8.3⁰C) 
rise in cooling. Under extreme conditions, slight variances in the temperature may be noted. 
 
 
 
 
 
 

Содержание KlassKeeper KKV024

Страница 1: ...Last Revised April 2020 Installation Operation Maintenance Manual KlassKeeper Heat Pump KlassKeeper Models KKV024 KKV048...

Страница 2: ...rant Charge 5 Unit Clearances 5 INSTALLATION 6 Delivery and General Installation Checklist 6 Location 6 Cabinet Placement 6 Dry Walling when required 7 Piping 7 Wiring 8 OPERATION 9 Inputs Outputs 9 O...

Страница 3: ...st Revised April 2020 Installation Operation and Maintenance Manual is Subject to Change without Notice MAINTENANCE 17 Inspect Filters 17 Check Fan motors annually 17 Visual Inspection 17 Amperage Che...

Страница 4: ...cting the unit to conditions of this nature may result in significantly reduced performance reliability and operational life The unit is intended for interior use only and should be stored indoors at...

Страница 5: ...Keeper Installation Operation and Maintenance Manual 4 Copyright 2013 CGC Group Inc Last Revised April 2020 Installation Operation and Maintenance Manual is Subject to Change without Notice Unit Dimen...

Страница 6: ...Charge oz 40 45 50 60 Consult factory Unit Clearances Clearances for the KlassKeeper units shall be provided such that the access panel swinging door opens and closes without obstruction to allow ser...

Страница 7: ...unit installation Specific site conditions may warrant variations in locations and dimensions 1 Remove packaging and inspect the unit Check for shipping damage or material shortage file a freight cla...

Страница 8: ...all screw must not be longer than the drywall thickness plus a maximum 3 8 Ensure drywall is not obstructing the swinging access door Piping CAUTION Piping must comply with all applicable codes and re...

Страница 9: ...bject to Change without Notice Wiring 1 Connect the wire harnesses between the chassis ERV and cabinet as per the below diagram 2 Connect the power plug to the receptacle in the cabinet Wire Harness T...

Страница 10: ...dry contacts on the third party controller or thermostat Analog Inputs TH1 Discharge Air Temperature TA TH2 Refrigerant Temperature TR TH3 Leaving Water Temperature TW TH4 Exhaust Entering Air Tempera...

Страница 11: ...will also be opened whenever there is a cool call in place To bring on the second stage of cooling contact DI3 on the unit controller must be closed through a dry contact on the unit mounted third pa...

Страница 12: ...ED Flashcode The Flex controller has a multi colored Alarm LED that is used to communicate the previous alarm if any through the use of flashcodes If there have been no alarms this LED will be green I...

Страница 13: ...ompressor has been running for three minutes a low pressure alarm will be activated the compressorwill be turned off the general alarm contact K7 will be energized a flashcode of 5 will be displayed a...

Страница 14: ...ovides information about the unit s operation The first button on the left allows the user to scroll through three separate screens Screen 1 This screen provides information on the alarm status of the...

Страница 15: ...m Central heat injection and rejection equipment is automatically controlled via a CGC control panel or equivalent to provide the required loop water temperature for correct KlassKeeper Bulldog Heat P...

Страница 16: ...speed the unit must be placed into cool mode Clean Unit Filters Check to ensure the unit filters are clean each KlassKeeper unit is equipped with three filters a pleated supply air filter and a wire f...

Страница 17: ...system problems may cause less than optimum operation In the event that the qualified commissioning agents suspect there is an operational problem with the heat pump they need to inform the factory im...

Страница 18: ...esh air filter unscrew the corresponding access panel on the left of the cabinet and slide the filter out Slide a new filter into place make certain the arrow on the filter is pointing in the directio...

Страница 19: ...t is reset or power is disconnected for 20 seconds NOTE If the heat pump must be reset more than twice check the unit for a dirty air filter abnormal entering water temperature inadequate water flow d...

Отзывы: