background image

www.bullard.com

6

Maintaining the 

fr

ee-

air Pump / 

tr

oubleshooting 

guide

9.  With the air flowing, put on the respirator by following the directions in the 

respirator manufacturer’s Instruction Manual.

YOU ARE NOW READY TO ENTER THE WORk AREA.

10.  When finished working, leave the work area wearing the respirator with the air 

still flowing. Once outside the contaminated area, remove the respirator, turn the 

pump off, then disconnect the air supply hose using the quick-disconnect couplings.

See the respirator’s Instruction Manual for proper inspection, maintenance 

and storage procedures for the respirator you are using.

Maintaining the free-air Pump

FOR THE PUMP TO OPERATE AT ITS OPTIMUM PERFORMANCE LEvEL, THE 

FOLLOWING ROUTINE MAINTENANCE PROCEDURES MUST BE PERFORMED.
FOR THE SPECIFIC LOCATION OF THE PUMP COMPONENTS REFERRED TO 

BELOW, SEE THE LIST OF PUMP COMPONENTS ON PAGE 4.

Maintaining the air Motor

The air motor is a rotary 4-vane type. The vanes require no adjustment and will last 

5,000-15,000 hours if properly maintained.

1. Flush MOTOR (9):

If motor is sluggish or inefficient, flush with LOCTITE SAFETY SOLvENT, or any 

non-toxic, nonflammable industrial cleaning solvent).

Use the following directions to flush the motor:

a. Shut-off the pressure into the air motor and disconnect the airline from the 

DRIvE AIR INLET (13).

b. Locate the pump in a safe area. Solvent will spray from the exhaust port 

during flushing. Protect your face and eyes from the spray.

c. Remove the PLUG (11) and pour several teaspoons of solvent into the opening.
d. Replace the PLUG, reconnect the airline back to the DRIvE AIR INLET. Turn 

the pressure back on. Run the pump at a very low speed (10-20 RPM) for 

approximately one minute or until all the solvent is flushed.

note: 

Motor bearings are grease packed and sealed. They require no 

maintenance.

Maintaining the Pump

Pump is rotary 4 vane type. The vanes require no adjustment and will last 5,000 to 

10,000 hours if properly maintained.

1.  Maintain FILTERS

- Dirty filters restrict outlet air flow and can cause the motor to overload or 

cause premature pump failure.

- Replace CARBOFINE OUTLET FILTER CARTRIDGE (6) at least once every 200 

running hours (Catalog No. S17101).

- Replace INLET FILTER (1) at least once every 500 running hours to maintain 

proper pressure and full air flow. To check the filter - while running the 

pump, momentarily remove the FILTER (1) from the INLET PIPE (2). If the 

motor speeds up or the outlet pressure shown on GAUGE (5) increases, the 

filter needs replacement.

2.  Flush PUMP if necessary

Should dirt, foreign particles, moisture or oil be permitted to enter, the vanes 

will become sluggish, resulting in a lowering of outlet air pressure. Flush the 

pump with LOCTITE SAFETY SOLvENT. (DO NOT USE kEROSENE).

Pump should be operated for at least a few minutes every one to two weeks 

to reduce the likelihood of rust film forming in the rotor.

If pump remains idle in humid environment for some time, FLUSHING may be 

required to remove rust film in chamber and rotor slots.

Use the following directions to flush pump:

a. Turn-off THROTTLE vALvE (10) to stop the pump before flushing.

b.  Before flushing, disassemble and remove the following parts from the pump:

- Respirator air supply hose(s)
- Inlet Filter and Pipe Stand
- Outlet Filter Jar and Outlet Filter

c.  With the pump running, pour several teaspoons of solvent into the pump’s 

inlet port. Repeat the flushing if necessary.

 WaRning

RUN THE PUMP FOR A SUFFICIENT TIME TO PURGE ALL TRACES OF THE SOLvENT 

BEFORE REPLACING THE FILTERS, RECONNECTING THE AIR SUPPLY HOSE(S) 

AND USING THE RESPIRATOR.

3.  AvOID ExCESSIvE SPEEDS and PRESSURE

- Avoid running above the 25 psig range for any length of time.

note: 

NEvER lubricate this oil-less pump. BEARINGS are grease packed 

and sealed. They require no further lubrication.

ensuring Pump Performance

To make sure your pump will perform properly:

1. Always locate the pump’s air inlet in a clean, breathable air environment.

2. DO NOT contaminate inlet air with exhaust air from air motor

3. Change OUTLET FILTER every 200 running hours.

4. Make sure RELIEF vALvE is fully seated (no bleed-off).

5. Always check Respirator Air Supply Hoses to make sure they are free of kinks.

6. Set incoming compressed drive air at 85 psig or higher. Set output air pressure 

as specified in respirator owner’s manual.

troubleshooting guide

outlet PRessuRe too high

- Adjust THROTTLE vALvE (10)

- Check for kinked air supply hoses

- Reset pressure adjustment valve

outlet PRessuRe too loW

- Adjust THROTTLE vALvE to increase motor speed

- Check for clogged INLET FILTER

- Check that outlet filter jar is screwed on tight

- Check for clogged OUTLET FILTER

- Check pressure relief valve and adjust if necessary

- Check drive air inlet pressure

- Check for leaks in air hose

- verify proper pressure range for your respirator

- verify that respirator and hose are connected when gauge reading is taken

- Check to see that gauge is functioning properly

- Flush pump with LOCTITE SAFETY SOLvENT

Содержание Free-Air ADP3CA

Страница 1: ...sured at all times to workers wearing Type C or CE continuous flow airline respirator hoods or tight fitting half or full face masks The ambient air is filtered through a medium efficiency inlet air f...

Страница 2: ...atory protection is enhanced when air flow available to the respirator wearer is above the NIOSH required minimums Model ADP3CA Pump Performance Table Incoming Drive Air Pressure Maintained at 95 psig...

Страница 3: ...e with this pump contact Bullard s customer service department at 877 bullard 3 Airline respirators used withthis pump must not be worn in any atmosphere immediately dangerousto life or health or from...

Страница 4: ...ed to below see the list of pump components to the left Assembling the Free Air Pump 1 Remove assembly from plywood shipping board and attach four rubber feet through four holes in skid 2 Install stan...

Страница 5: ...p is equipped with a 2 ft stand pipe to keep the intake away from the air motor exhaust port If the inlet filter cannot be placed at a source of clean breathable air install Bullard s 50 foot Inlet Ex...

Страница 6: ...ER 1 from the Inlet PIPE 2 If the motor speeds up or the outlet pressure shown on GAUGE 5 increases the filter needs replacement 2 Flush PUMP if necessary Should dirt foreign particles moisture or oil...

Страница 7: ...be defective subject to the following limitations a Free Air Pump must be returned to the Bullard factory with shipping charges prepaid b Free Air Pump must not have been misused subjected to negligen...

Страница 8: ...aterials Bullard may refuse to accept the return of any product suspected of being contaminated 4 Products returned including those under warranty must be shipped with all transportation charges prepa...

Отзывы: