![Buhnen HB 700 Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/buhnen/hb-700/hb-700_operating-manual_2828288010.webp)
10
4.4
Adjusting the spray pattern (HB 700 Spray only)
The spray pattern is altered by adjusting the spray air.
Set the optimum spray pattern by turning the spray-air choke (14) in the protective sleeve
(13):
• Turning it clockwise decreases the spray-air pressure.
• Turning it anticlockwise increases the spray-air pressure.
4.5
Automatic temperature reduction (ACE)
Unnecessary thermal loading of the melt should be avoided. The device therefore swit-
ches to standby mode at reduced temperature when the trigger has not been actuated for
a considerable time (paused operation).
In the condition as supplied the temperature is reduced by 72 F / 40°C after 30 minutes’
paused operation. The programming of the relevant parameters is described in Section
3.3.2.
Briefly actuate the trigger or the Up or Down button to quit standby mode. The device
immediately reheats to working temperature.
4.6
Switching off
1. Press the Start/Stop button (6) for approx. 1 s until the display goes out.
2. Adjust the operating pressure down to “0” with the pressure regulator (3) or disconnect
the compressed-air supply.
5
What if...
This Section summarises the status and error messages and provides help in eliminating
errors.
If malfunctions occur please check first
• hat the power supply and
• compressed-air supply are functioning correctly, and
• whether there is mechanical damage to the device or supply lines (power supply, com-
pressed air).
If you find any mechanical damage, the device may in no circumstances be started up
again. Have it checked and repaired by a qualified service agent.
5.1
Status and error messages in the display
Indication
Cause
Action
Decimal point on left flashes
Warm-up phase active
The warm-up phase is ended when a tem-
perature 2 °F / 2°C short of the set working
temperature has been reached.
Decimal point on right is lit
Setpoint lowering active
See parameters P1 and P2 (Section 3.3.2)
ERR
Permitted maximum tem-
perature of 500 °F / 260 °C
exceeded
Allow to cool down
F1L
Sensor fault, short circuit
Have the device checked by a qualified
service agent.
F1H
Sensor fault, sensor breakage
Have the device checked by a qualified
service agent.
--
Keylock active
See parameter P19 (Section 3.3.2)
EP
Data loss in parameter memory The regulator must be replaced by a quali-
fied service agent.
What, if…
Содержание HB 700
Страница 1: ...Operating Manual Hot Melt Applicator HB 700 HB 700 Spray...
Страница 19: ...19...