3
Standards, regulations and directives
S 32/5 – 6 720 804 007 (2014/10)
9
3
Standards, regulations and directives
4
Moving the tank
▶ Position the dolly at the back of the packed tank.
▶ Secure the tank to the means of transportation with a strap.
▶ Transport the tank to the installation location.
▶ Only remove the tank from the packaging at the installation location.
Fig. 5
Transporting with a dolly
5
Installation
The tank is delivered fully assembled.
▶ Check that the tank is complete and undamaged.
5.1
Tank installation
5.1.1
Requirements for installation location
▶ Place the DHW tank on a plinth if there is any danger of water
collecting on the floor of the setup site.
▶ The installation site must be a dry and frost-free room.
▶ Observe the minimum room height (
Tab. 6, page 8) in the
installation room. No minimum wall clearance required.
▶ Maintain a distance of 2" (51 mm) from heated pipes and
combustible surfaces.
5.1.2
Positioning the tank
▶ Unpack the tank by removing the wrap, wooden boards and foam pad
on the top.
▶ Lay the foam pad on the floor to serve as a mat.
Observe all national, state, and local code, regulations
and standards applicable to installation and operation of
the tank!
All electrical components must be approved for the USA
and Canada.
WARNING:
Risk of injury from carrying heavy loads and
inadequately securing loads for transport!
▶ Use suitable means of transportation, e.g. a dolly
with strap.
▶ Secure the load against falling.
Where possible, do not remove the tank from its
packaging until it has reached the installation location.
This ensures protection during handling.
6 720
8
00 0
3
5-0
3
.1ITL
NOTICE:
Risk of damage from inadequate load-bearing
capacity of the supporting substructure or unsuitable
floor surface!
▶ Ensure that the installation area is level and offers
sufficient load-bearing capacity.
NOTICE:
Risk of damage from stress cracking and
corrosion!
▶ Position the tank in a dry room free from the risk of
freezing.
▶ Install the tank only in closed-loop, unvented
hydronic heating systems.
▶ Open expansion vessels may NOT be used with this
tank.
NOTICE:
Install an adequate drain pan if required by
code, or if a leak could result in property damage. Follow
drain pan manufacturer's instructions.
A minimum 19" (480 mm) clearance is required above
the DHW tank in order to remove the magnesium
anodes.