2
Product Information
S 32/5 – 6 720 804 007 (2014/10)
7
2.6
Technical Data
Unit
S 32/5
Tank capacity
Capacity (overall)
gal
(l)
30.0
(114)
Max. flow rate
gpm
(l/min)
3.2
(11.4)
Max. DHW temperature
°F
( °C)
203
(95)
Maximum hot water operating pressure
psi
(bar)
150
(10.3)
Standby heat loss (149 °F (65 °C) DHW temperature, 68 °F (20 °C) Room
temperature)
°F/h
(K/h)
1.0
(0.55)
DHW tank performance
Domestic cold water inlet temperature
°F
( °C)
50
(10)
Domestic hot water outlet temperature
°F
( °C)
140
(60)
DHW temperature rise
°F
( °C)
90
(50)
Heat exchanger supply temperature (heating water)
°F
( °C)
176
(80)
Flow rate (heating water)
gpm
(l/h)
8.0
(1820)
Pressure drop (heating water)
f o h
(mbar)
1.9
(57)
Continuous rating
gph
(l/h)
137
(519)
gpm
(l/min)
2.28
(8.6)
Amount that can be drawn off in the first hour
gph
(l/h)
165
(625)
Maximum heat output
btu/hr
(kW)
87 959
(26.4)
Heat exchanger
Content
gal
(l)
1.9
(7.2)
Surface area
ft
2
(m
2
)
10-3/4
(1.0)
Maximum heating water temperature
°F
( °C)
230
(110)
Max. operating pressure, heat exchanger
psi
(bar)
232
(16)
Table 5 Technical Data
Содержание S32/5
Страница 34: ...10 S 32 5 6 720 804 007 2014 10 34 Notes ...
Страница 35: ...10 S 32 5 6 720 804 007 2014 10 35 Notes ...
Страница 36: ......