Assembly and Installation
4
7
We reserve the right to make any changes due to technical modifications!
Installation and Maintenance Instructions Logalux S 120 „US“• Issue 07/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
4
Assembly and Installation
Level tank by adjusting the leveling bolts under the
tank (Fig. 5).
4.1
Safety Requirements
Critical Values
*
In the overall system, it is necessary to install a boiler pressure
relief value, expansion tank and P and T valve for the tank.
Fig. 5
Adjusting tank leveling bolts (sample picture)
ATTENTION!
TANK DAMAGE
When exceeding critical values.
One must adhere to the following
critical values for safe operation.
Temperature:
Heating water (boiler)
230 °F
Domestic water (tank)
203 °F
Operating pressure:
Heating water (boiler)*
87 psi
Domestic water (tank)
145 psi