Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Maintenance
12
Removal of gas burner:
1.
Shut-off main gas piping shut off valve.
2.
Remove the screws from the boiler front access
panel (Fig. 30,
Item. 1
) and remove the boiler front
access panel (Fig. 30,
Item. 2
).
3.
Turn the gas control knob (Fig. 31,
Item. 1
)
counterclockwise to "OFF". Do not force.
Fig. 30
Removal of boiler jacket front panel
Item. 1:
Screws
Item. 2:
Boiler jacket front panel
1
2
1
Fig. 31
Gas control valve
Item. 1:
Gas valve knob (set to “ON“)
1
WARNING!
DANGER
due to explosion of the gas.
z
Wait five (5) minutes to clear out any
gas. Then smell for gas, including near
the floor. If you smell gas, STOP!
Follow "B" in the safety information on
page 28. If ou do not smell gas, go to
the next step.