Instructions for High Altitude Conversion

9

We reserve the right to make any changes due to technical modifications!

Instructions for high altitude conversion for sealed combustion gas boiler GA124 • Issue 

03/2005

Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de

10.

Check manifold pressure.  Set the manifold pressure 
according to the values in Table 3.  To adjust the 
manifold pressure (Fig. 9, 

Item. 5

), remove the 

capscrew from the gas control.  Turn the pressure 
regulating adjusting screw clockwise to increase, or 
counterclockwise to decrease the manifold 
pressure.  This adjustment must be made while the 
boiler is in operation.

.

11.

After adjustment, record pressure in the start-up 
procedure, and install the capscrew on the gas 
control (Fig. 9, 

Item. 5

).

12.

Observe the pilot flame (Fig. 10, 

Item. 2

) through 

viewing port (Fig. 8, 

Item. 1

) in the burner cover 

plate.  The flame should envelop the flame sensor ½ 
- 1-½ inch, see (Fig. 10, 

Item. 1

).  If the pilot flame is 

satisfactory then go to step 13.  If the pilot flame is 
too small or too large, adjust the pilot using pilot 
adjustment.  Turn the inner adjustment screw 
(Fig. 9, 

Item. 4

) clockwise to decrease, or 

counterclockwise to increase the pilot flame.  After 
adjustment, replace the cover screw and tighten 
firmly (Fig. 9, 

Item. 4

).

13.

Observe the main burner flame (Fig. 11, 

Item. 1

through the viewing port (Fig. 8, 

Item. 1

) in the 

burner cover plate.  The flame should have a 
smooth, firm contour and must be mostly blue in 
color.  If the main flame is satisfactory, go to step 14.  
If the main burner flame is lazy, yellow, or lifting off 
the burners, turn the gas control knob (Fig. 9, 

Item. 1

) clockwise to "OFF".  Shut off the main gas 

piping shutoff valve.  Disconnect all electric power to 
the appliance and call your service technician or gas 
supplier.

14.

The ignition safety shutoff must be tested.  Test the 
safety shutoff by shutting off the main gas piping 
shutoff valve.  The main burner and pilot flame 
(Fig. 10, 

Item. 2

) will extinguish.  Within six (6) 

seconds the gas control main gas solenoid should 
close and make an audible sound.  The ignition will 
spark.
After 90 seconds, the module should go into lock out 
mode and the spark should stop.  Disconnect the 
electric power to the appliance.  Open the main gas 
shutoff valve.  Turn on the electric power to the unit.  
A normal operating sequence should occur.  If the 
gas control functions satisfactorily then go to step 
15.  If the gas control does not function satisfactorily, 
immediately turn the gas control knob (Fig. 9, 

Item. 1

) clockwise to "OFF".  Shut off the main gas 

GA124 

Natural gas

[inch W.C.]

Propane

[inch W.C.]

17

3.6

8.9

23

3.6

9.9

30

3.5

9.5

Table. 3  Required manifold pressure

Fig. 10

Proper pilot setting

Item. 1:

1/2“ to 1-1/2“

Item. 2:

flame

1

2

Fig. 11

Main burner flame profile

Item. 1:

flamelet profile

1

Содержание Logano GA124-17

Страница 1: ...nstalled by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction and in accordance with the requ...

Страница 2: ...Conversion data plate to be filled out and affixed to the appliance Conversion instructions Technical documents WARNING DANGER Denotes a possible severely dangerous situation where without proper caut...

Страница 3: ...3 Remove jacket panel screws Fig 1 Item 1 from left and right side tilt forward top of front jacket panel Fig 1 Item 2 then lift up from the bottom and remove 4 Turn the gas control manual knob Fig 2...

Страница 4: ...he flame roll out switch Fig 4 Item 3 10 Remove the burner tray cover plate screws and remove this cover plate Fig 4 Item 4 11 Remove burner tray mounting nuts Fig 4 Item 1 and take entire burner tray...

Страница 5: ......

Страница 6: ...ter to measure the supply pressure 26 Remove the manifold pressure tapping plug Fig 7 Item 3 from the gas control Install a test fitting and hook up a manometer to measure the manifold pressure 27 Ope...

Страница 7: ...ll not turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water...

Страница 8: ...and then the main burners should light If the main burners do not light shut off the main gas piping shutoff valve Shut off all electric power to the appliance and call your service technician or gas...

Страница 9: ...urner flame Fig 11 Item 1 through the viewing port Fig 8 Item 1 in the burner cover plate The flame should have a smooth firm contour and must be mostly blue in color If the main flame is satisfactory...

Страница 10: ...essure tabs in the gas control and replace the plugs 19 Repeat steps 1 to 6 and 13 to place the appliance back in operation Check the plugs in the gas control with a soap and water solution If no leak...

Страница 11: ...rve the right to make any changes due to technical modifications Instructions for high altitude conversion for sealed combustion gas boiler GA124 Issue 03 2005 Buderus Heiztechnik GmbH http www heizte...

Страница 12: ...3 552 1100 Fax 603 584 1681 www buderus net BBT North America Corporation reserves the right to make changes without notice due to continuing engineering and technological advances Heating Contractor...

Отзывы: