Applications manual
|
27
GB125 Concentric Vent
Design Manual
GB125 Concentric Vent Design Manual | 05.2009
Technical specifications are subject to change without prior notice
Connecting a UB Flex Pipe with Rigid Pipe
Under certain circumstances it may be necessary to
connect a rigid pipe with a UB-Flex pipe. Use the
following union:
Table 15
Part Number
Description
87094672
Connector from GAK rigid pipe to UB Flex pipe
The flexible pipe UB Flex can only be combined with the
GAK system. Do not exceed the maximum vent length
permitted based on the size of the boiler (Table 2)
The rigid pipe always has to be on the top and
the UB Flex pipe on the bottom of the union.
The union consists of a main body with a gray gasket
installed (Fig. 26, item 2), 1 split ring (item 4), 1 red
gasket (item 3), and 1 threaded bottom piece (Item 5).
Item 1 is the rigid pipe, and item 6 the corrugated UB Flex
pipe.
Only the perforated section of the UB Flex pipe can be
connected, and it is necessary to cut off any smooth
section. Make cuts perfectly perpendicular to the pipe.
Disassemble the union and observe the arrow on the
main body dictating the direction of the flue gases. The
gray gasket must face up.
Slide the threaded ring with the threads facing up over
the UB flex pipe. Slide the split ring over the UB flex pipe
with the flange facing up, and snap into the second grove.
Slide the red gasket over the corrugated UB flex pipe and
snap into the very first grove.
Now insert the pipe so prepared into the main body and
screw the threaded ring in until hand tight.
Coat the gray gasket and the mating pipe with
CENTROCERIN® and insert the rigid pipe into the union
by slightly turning the pipe into the gasket.
Install a chimney spacer on the main body of the union.
Fig. 26 UB flex pipe to rigid pipe connection
1 Rigid vent pipe (must be at the top)
2 Center piece (arrow pointing in direction of flue gases)
3 Red gasket
4 Split ring
5 Screw bottom
6 UB Flex pipe, cut off smooth section