4
Placing the boiler
Logano G234X – 6 720 811 233 (2017/02)
9
4
Placing the boiler
This section explains how to set up and position the boiler correctly at
the installation location.
4.1
Installation location requirements
4.2
Clearances
Position the boiler with the recommended wall clearances. Reducing
these to the minimum clearances makes the boiler more difficult to
access.
The base or foundation on which the boiler is to stand must be perfectly
flat and level. The boiler may stand on a base made of combustible
material, but not on carpet.
A space of at least 33 inches (840 mm) is required in front of the boiler
with the door open to allow sufficient accessibility for operation and
maintenance. When the door is closed, a minimum clearance of 2 inches
(50 mm) is required at the front and sides, a wall clearance of 6 inches
(155 mm) is also required for the flue pipe and 30 inches (762 mm)
clearance to the ceiling.
Fig. 6
Wall clearances in the boiler room
[1]
Closed door
[2]
Open door
4.3
Leveling the boiler
The boiler must be leveled horizontally and vertically to prevent air
pockets forming inside.
▶ Level the boiler both horizontally and vertically using a spirit level.
▶ Insert metal shims underneath if necessary.
Fig. 7
Leveling the boiler (example)
DANGER:
Danger posed by explosive and combustible
materials!
▶ Never use or store easily flammable materials (paper,
curtains, clothing, thinners, paints etc.) near the
boiler.
▶ Maintain a clearance of 16 inches (415 mm) from the
boiler.
NOTICE:
Risk of system damage due to freezing!
▶ Install the heating system that it will not be exposed
to freezing conditions.
NOTICE:
Damage to the building due to insufficient load
capacity of the floor!
▶ Before setting the boiler up, check the load capacity
of the floor.
NOTICE:
Boiler damage due to contaminated
combustion air.
▶ Do not use cleaning agents that contain chlorine or
halogenated hydrocarbons (e.g. in spray cans,
solvents and cleaning agents, paints, glues).
▶ Avoid excessive dust accumulation (building dust).
Wall clearance
Dimension
[inch]
[mm]
A
33
840
B
6
155
C
2
50
Table 6 Wall clearances
Where applicable, allow extra wall clearances for
additional components such as a DHW tank, pipe joints,
vent pipe silencer or other components on the flue gas
side, etc.
NOTICE:
Risk of system damage due to contamination!
▶ If the boiler is not to be installed immediately, protect
the connections from entry of dirt.
1
2
6 720 806 028-05.1T
6 720 806 028-04.1T
Содержание G234X/38
Страница 34: ...10 Logano G234X 6 720 811 233 2017 02 34 Notes...
Страница 35: ...10 Logano G234X 6 720 811 233 2017 02 35 Notes...
Страница 36: ......