background image

5

 

Boiler installation

Logano G234X – 6 720 811 233 (2017/02)

15

Total air supply from inside the building

Make sure that the installation room has two permanent air vents that 
are connected to one or more other rooms. When calculating the cross-
sectional areas of the vent apertures, the total burner output of all gas-
fired appliances in the connected rooms must be taken into account. 
Each vent must have a minimum cross-section of one square inch per 
1000 Btu/h (2200 mm

2

/kW) of the total burner output of all gas-fired 

appliances inside the connected rooms. Make sure that the cross-
sectional area of each vent is at least 100 square inches (0.06 m

2

). One 

of the vents must be no more than 12 inches (300 mm) from the ceiling 
and the other no more than 12 inches (300 mm) from the floor of the 
installation location, measured from the outer edge of the vent opening. 
The smallest dimension of all air intake and outlet openings must be not 
less than 3 inches (80 mm).

Total air supply from outside the building

Make sure that the installation location has two permanent air vents, one 
of which must not be more than 12 inches (300 mm) from the ceiling 
and the other not more than 12 inches (300 mm) from the floor of the 
installation location, measured from the outer edge of the vent opening. 
The vents must be connected either directly or via air ducts to the 
outside or to rooms that have an unobstructed connection to the open 
air (e. g. crawl space or attic). The smallest dimension of all air intake 
and outlet openings must be not less than 3 inches (80 mm).

• If there is a direct connection to the outside, each opening must have 

a minimum cross-section of one square inch per 4000 Btu/h 
(550 mm2/kW) of the total combustion output of all gas-fired 
appliances inside the closed room.

• If there is a connection to the outside through horizontal ventilation 

ducts, each opening must have a minimum cross-section of one 
square inch per 4000 Btu/h (550 mm

2

/kW) of the total burner 

output of all gas-fired appliances inside the closed room.

• If there is a connection to the outside through vertical ventilation 

ducts, each opening must have a minimum cross-section of one 
square inch per 2000 Btu/h (1100 mm

2

/kW) of the total burner 

output of all gas-fired appliances inside the closed room.

• If the openings are connected to ventilation ducts, the ducts must 

have the same cross-section area as the openings to which they 
connected.

5.7.2

Requirements for connection to chimneys or flue gas 
systems

The flue connection must comply with the regulations of the National 
Fuel Gas Code NFPA 54, Part 7, Venting of Equipment, and the local 
building codes. In Canada the regulations of CAN/CSA B 149.1 as well as 
local building codes apply.

Flue connections of boilers with natural venting must not be connected 
with any component of a mechanically operated flue gas system (blower-
assisted) that operates with overpressure. 

The cross-section of the flue connection must not be less than that 
specified in Tab. 10.

If the boiler will be connected to a masonry chimney:
▶ Inspect the chimney thoroughly beforehand. 
▶ The chimney must be clean, in compliance with construction codes 

and of sufficient dimensions.

Chimneys with an internal liner are preferred and are only permitted if 
the liner complies with all national, state and local construction codes. 

Liners of fire-glazed brick with moisture-proof joints and liners of 
corrosion-resistant material are recommended.

Contact the local gas supply utility for advice and recommendations for 
flue connection and chimney liners. A flue pipe of single-walled sheet 
metal is required for flue connections for type II appliances. 

An adequate chimney height in compliance with the tables of the 
National Fuel Gas Code, ANSI Z 223.1, is required.

Disconnecting a boiler from a common flue gas system

If an existing boiler is disconnected from a common flue gas system, the 
flue gas system is now oversized. Proper venting for the remaining 
heating systems is then no longer guaranteed.

If impurities in the combustion air are possible (e. g. 
installation near swimming pools, dry cleaners or 
hairdressing salons), sealed combustion is 
recommended.

Boiler size

Diameter of the flue gas connector 

[inch]

[mm]

38

7

178

45

7

178

55

7

178

64

8

203

Table 10  Cross-section of the flue gas connection

Содержание G234X/38

Страница 1: ...em is carried out by an unqualified person this may result in a fatal injury or property damage Follow the instructions in this installation and maintenance manual exactly If you require assistance or...

Страница 2: ...ting the flue connector 14 5 7 1 Check openings for combustion air supply and venting 14 5 7 2 Requirements for connection to chimneys or flue gas systems 15 5 7 3 Installing the flue pipe 16 5 7 4 Co...

Страница 3: ...is not be fitted with a barometric damper or a thermally controlled vent damper downstream of the flue connector Do not tamper with remove or attempt to repair the flue gas shutoff switch When replac...

Страница 4: ...ns or repairs 2 Product Description This installation and maintenance manual contains important information for the safe and correct installation initial commissioning and maintenance of this boiler T...

Страница 5: ...fashion Dispose of any components of the heating system that require replacement in an environmentally responsible fashion at an approved landfill Notice regarding environmental protection and dispos...

Страница 6: ...0 11 16 25 10 16 2 10 16 38 7 16 729 465 137 147 348 650 66 1034 975 6 720 806 028 02 1T Boiler size Unit 38 5 45 5 55 6 64 7 Ignition heat load MBTU hr 160 187 228 266 kW 46 9 54 8 66 8 78 0 Nominal...

Страница 7: ...r of injectors Main gas orifice identification Rated orifice pressure for natural gas 0 8500 ft 0 2591 m In W C mbar 38 3 3 70 3 0 7 6 45 3 3 70 4 1 10 4 55 4 3 50 4 6 11 5 64 4 3 80 4 4 10 9 Table 4...

Страница 8: ...boiler and roll it on additional pipes to the installation location Fig 5 Place the boiler in its final position Fig 5 Transporting the boiler on rollers NOTICE Risk of system damage from impact shoc...

Страница 9: ...l the boiler both horizontally and vertically using a spirit level Insert metal shims underneath if necessary Fig 7 Leveling the boiler example DANGER Danger posed by explosive and combustible materia...

Страница 10: ...e right side NOTICE Risk of boiler damage due to moisture Protect the individual components of the control system and the ignition system from damp dripping water water spray rain during installation...

Страница 11: ...le regulations Mount an ON OFF switch near the boiler Fig 10 Main power switch by customer DANGER Risk of fire from flammable materials Maintainaclearanceof2inches 51 mm frompipes carrying hot water a...

Страница 12: ...l code We recommend installing a manual shutoff valve in the main gas pipe to the boiler The gas pipes must be fastened outside the boiler The gas supply pipe is designed for a gas connection on the r...

Страница 13: ...ersionkitsforconvertingtheboilerfromnaturalgas to propane gas can be obtained from Bosch Do not attempt to convert the appliance without the approved Buderus parts and the relevant technical documenta...

Страница 14: ...building codes In Canada the regulations in accordance with CAN CSA B 149 1 and 2 Installation Codes apply NOTICE System damage due to faulty safety valve Do not install the safety valve until the lea...

Страница 15: ...the outside through vertical ventilation ducts each opening must have a minimum cross section of one square inch per 2000 Btu h 1100 mm2 kW of the total burner output of all gas fired appliances insi...

Страница 16: ...oles provided in the vent damper 1 Fasten vent damper to the flue connector adapter with three 3 corrosion resistant sheet metal screws A Seal all unused openings of the common flue gas system B Perfo...

Страница 17: ...s are permitted to carry out electrical work Beforeopeningtheappliance Disconnectitfromthe power supply via the ON OFF switch or the appropriate building fuse Take measures to ensure that the heating...

Страница 18: ...lose the gas shutoff valve seal the leaks and repeat step 6 8 Close the gas shutoff valve Remove the screw plug from the gas supply pressure test point 2 on the gas valve in order to measure the gas s...

Страница 19: ...and subsequent incorrect operation Risk of fire and explosion from failure to observe the startup instructions Read the startup instructions carefully before commissioning DANGER Risk of fatal injury...

Страница 20: ...32 4 mbar Record the measured values in the commissioning report page 23 11 Check nozzle pressure Set the orifice pressure according to Table 11 while the boiler is operating To do so remove the safet...

Страница 21: ...21 Disconnecttheheatingsystemfromthepowersupply Openthegas shutoff valve Switch on the power supply for the appliance A normal operating cycle must follow If the gas valve operates correctly Proceed t...

Страница 22: ...4 Fig 28 Checking temperature control 1 Adjustment keypad 6 6 Shutting off gas supply to boiler Set the room thermostats to the lowest setting Disconnect the heating system from the power supply befor...

Страница 23: ...rifice pressure and adjust if necessary inches W C or mbar Page 20 Meas value _____________________________ Unit _____________________________________ 7 Leak test during operation Check ignition flame...

Страница 24: ...gulations are strictly observed To protect the environment we use the best possible technology and materials taking into account economic points of view Packaging method For the packaging we participa...

Страница 25: ...e boiler for cleaning Shut down the heating system Section 7 1 page 24 Remove front wall of boiler Fig 18 page 18 Turn the gas valve ON OFF knob 1 clockwise to the OFF position Do not use excessive fo...

Страница 26: ...on the studs Fig 32 Removing the burner 1 Retaining nuts 2 Studs with spacers 9 5 2 Cleaning the boiler with brushes mechanical cleaning Remove the boiler casing and thermal insulation check for damag...

Страница 27: ...ning the burner Remove burner Section 9 5 1 Check burner rods for dirt If necessary clean burner as described below Unscrew pilot burner unit Fig 35 1 from burner Disconnect pilot gas line 3 from pilo...

Страница 28: ...any other flammable or corrosive vapors and liquids Complete the maintenance log to confirm that all maintenance work has been carried out page 31 Sign the maintenance log and familiarize the owner w...

Страница 29: ...the If everything is OK replace pilot assembly No Heat requirement ended system switches off flue baffle closes End of troubleshooting Repeat procedure until heating system operates properly On model...

Страница 30: ...n flame Specified thermostat value control reached Main and ignition gas valves close gas burners ex tinguished vent damper if installed closes Ignition burner operation Ignition flame burns automatic...

Страница 31: ...ge 18 ___________ inches W C ___________ inches W C 8 Check for leaks during operation Page 18 9 Check the pilot burner flame Page 20 10 Check the main burner flame Page 21 11 Check the vent damper Pa...

Страница 32: ...Blocked vent switch Intermittent pilot dual valve combination gas control VR8304 Pilot burner Honeywell Main valve Pilot valve green blue white red GND MV MV PV GND PV MV PV MV 24V 24V 4 3 2 1 Ref no...

Страница 33: ...ulator To Pilot Burner Spark Gas valve Main Pilot PV PV MV GND MV S8600H GND PV PV MV MV 24V 24VGND K1 TR High Limit Flame roll out safety shutoff switch K2 B2 L2 N L 24V AWG 18 WIRE 120 VAC Wiring Sc...

Страница 34: ...10 Logano G234X 6 720 811 233 2017 02 34 Notes...

Страница 35: ...10 Logano G234X 6 720 811 233 2017 02 35 Notes...

Страница 36: ......

Отзывы: