Liquid Propane conversion

Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!

8

B

Disconnect the boiler from the power supply.

B

Check the exterior tightness of new conduit sections 
up to and including the direct sealing point on the gas 
burner fitting. The maximum test pressure allowed on 
the input of the gas burner fitting is 60 " W.C. 
(150 mbar).

B

Check the input rates after converting the boiler to LPG 
to the values on the front page.

3.4

Inlet gas pressure

B

Open at least 1 thermostatic radiator valve if present to 
allow water to flow through the boiler. Do not switch on 
the boiler.

B

Close the gas shut-off valve. Loosen the screw plug on 
the inlet gas pressure testing nipple by 2 turns 
(

Æ

fig. 16, [1]).

B

Connect the pressure gauge connection hose to the 
testing nipple (

Æ

fig. 16, [2]).

B

Slowly open the gas shut-off valve.

The boiler and its individual shutoff valve must be 
disconnected from the gas supply piping system during 
any pressure testing of that system at test pressures in 
excess of 60 " W.C. (150 mbar). The boiler must be 
isolated from the gas supply piping system by closing its 
individual manual shutoff valve during any pressure 
testing of the gas supply piping system at test pressures 
equal to or less than 60 " W.C. (150 mbar).

Fig. 16 Measuring the gas supply pressure

B

Press on the control panel cover to open it.

Fig. 17 Opening the control panel

B

Switch on the boiler by setting the main switch to 
position “1” (

Æ

fig. 1, page 5).

B

Press the “Chimney Sweep” 

button and hold it for 

approx. 2 seconds until the display shows a decimal 
point.

B

Measure the gas connection pressure as soon as the 
“Burner” LED lights and enter this value in the start-up 
report.

The inlet gas pressure must be:
• for natural gas - min. 7.0 to 10.5 " W.C. (17.4 to 

26.1 mbar), nominal supply pressure 8.0" W.C. 
(19.9 mbar).

• for LPG - min. 8.0 to 13.0"  W.C. (19.9 to 32.3 mbar), 

nominal supply pressure 11.0"  W.C. (27.4 mbar).

B

Press repeatedly the “Service” 

e

 button until the 

temperature indication is displayed.

B

Press the “Chimney Sweep” 

button to end the 

measurement procedure.

B

Close the gas shut-off valve.

B

Remove the connection hose again and tighten the 
screw plug on the testing nipple.

B

Open the gas shut-off valve again.

DANGER: 

Risk of explosion

B

Check for leaks before working on gas-
carrying components.

CAUTION: 

due to a short circuit.

B

Cover damageable parts before leak 
testing.

B

Do not spray the leak detection agent onto 
cables, plugs or electrical connection 
lines. Do not allow it to drip onto them 
either.

NOTICE

B

Contact the relevant gas utility company if 
the required inlet gas pressure is not 
available.

B

Install a gas pressure regulator before the 
gas burner fitting if the supply pressure is 
too high.

1

2

6720615033-017.1TD

6720615033-018.1TD

Содержание Condensing gas boiler

Страница 1: ...of the authority having jurisdiction The information in these instructions must be followed to minimize the risk of fire or explosion or to prevent property damage personal injury or death The qualifi...

Страница 2: ...rnings 3 1 4 Additional symbols 3 2 Parts list for converting the boiler to propane 4 3 Liquid Propane conversion 5 3 1 Shut down the boiler 5 3 2 Changing the gas valve assembly 5 3 3 Testing for gas...

Страница 3: ...e severe personal injury death or substantial property damage WARNING Indicates the presence of hazards that can cause severe personal injury death or substantial property damage CAUTION Indicates pre...

Страница 4: ...nverting the boiler to propane Conversion kit propane for the GB162 80 kW 100 kW 7746900499 includes assembly 774601703A 1 gas valve propane venturi orifice 774600958A orifice 871860872A 8 000ft 1 lab...

Страница 5: ...the boiler door 3 2 Changing the gas valve assembly B Loosen the screw connection on the gas valve fig 3 1 and pull the plugs fig 3 2 from the gas valve Fig 3 Undoing the connections to the gas valve...

Страница 6: ...746900499 B If the boiler is installed above 8 000 ft 2 440 m altitude the orifice needs to be changed Follow the instructions below Otherwise go to the next step Undo the 4 screws fig 9 1 and remove...

Страница 7: ...parts in reverse order When re installing the burner plate make sure that the notch is on the right hand side fig 15 Fig 15 Re installing the burner plate B Carry out the start up activities and compl...

Страница 8: ...r Fig 16 Measuring the gas supply pressure B Press on the control panel cover to open it Fig 17 Opening the control panel B Switch on the boiler by setting the main switch to position 1 fig 1 page 5 B...

Страница 9: ...crew fig 19 1 The adjustment screw is located behind the cover screw Fig 19 Setting the gas air ratio B Press repeatedly the Service e button until the temperature indication is displayed B Press the...

Страница 10: ...ler if any part has been under water Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control which has been under water...

Страница 11: ...smell for gas including near the floor If you smell gas STOP and see the safety information on page 10 If you do not smell gas go to the next step B Install the casing again B Open the gas shut off v...

Страница 12: ...6720615033 0005...

Отзывы: