KNX temperature control panel
12. COMMUNICaTION ObjECTS (CONTINUED)
12.1 list of objects (continued)
No.
Function
Object name
Size
Flags
13
Heating/Cooling
Cooling mode
1.002 (1 bit)
CW
Cooling mode active received from the bus
Only in 2-tube installations
1 = Cooling mode
0 = Cooling mode not active (default value)
14
Heating/Cooling
Heating mode
1.002 (1 bit)
CW
Heating mode active received from the bus
Only in 2-tube installations
1 = Heating mode active
0 = Heating mode not active (default value)
15
Heating/Cooling
Heating valve status
5.001 (1 byte)
CW
Heating valve open (%) received from the bus
Only in 4-tube installations
Default value = 0
16
Heating/Cooling
Cooling (Heating/Cooling) valve status
5.001 (1 byte)
CW
In 4-tube installation: Cooling valve open (%) received from the bus
In 2-tube installation: Cooling (if OBJ13 cooling mode = 1) valve open (%) or Heating valve open (%) received from the bus
Default value = 0
17
Heating/Cooling
Heating valve status
1.002 (1 bit)
CW
Heating valve open received from the bus
Only in 4-tube installations
1 = Heating valve open
0 = Heating valve closed (default value)
18
Heating/Cooling
Cooling (Heating/Cooling) valve status
1.002 (1 bit)
CW
In 4-tube installation: Cooling valve open received from the bus
In 2-tube installation: Cooling (if OBJ13 cooling mode = 1) or Heating valve open received from the bus
1 = Cooling (Heating/Cooling) valve open
0 = Cooling (Heating/Cooling) valve closed (default value)
19
Fan
Fan Speed
5.001 (1 byte)
CT
Fan speed (%) sent on the bus
Only if 1-byte Fan function is active
Default value = 0
20
Fan
Fan Speed 1
1.002 (1 bit)
CT
Fan speed 1 sent on the bus
Only if 1-bit Fan function is active
1 = Fan speed 1
0 = Fan speed off (default value)
21
Fan
Fan Speed 2
1.002 (1 bit)
CT
Fan speed 2 sent on the bus
Only if 1-byte Fan function is active
1 = Fan speed 2
0 = Fan speed off (default value)
22
Fan
Fan Speed 3
1.002 (1 bit)
CT
Fan speed 3 sent on the bus1 = Standby
Only if 1-bit Fan function bit is active
1 = Fan speed 3
0 = Fan speed off (default value)