BTCPower 350 KW EVSE Installation manual
Draft
Page 10 of 23
Modularity
Power can be switched from one
output to the other in increments of
45 kW
Ripple current
< 15 A p-p, Maximum allowable peak
to peak HVDC output current ripple,
1kHz bandwidth limited
< 15 A p-p, Maximum allowable peak
to peak HVDC output current ripple,
1kHz bandwidth limited
AC to DC Power Converter Fault Protection and Safety Features
Converter compliance matrix
Feature
Specification
Specification
HI pot withstand
UL 2231-1/2, UL 840
UL 2231-1/2, UL 840
Insulation resistance
UL 2231-1/2, UL 840
UL 2231-1/2, UL 840
Output voltage regulation
+/- 2%, no load
+/- 2%, no load
Over temperature
Self-protected and latched
Self-protected and latched
Input AC Over voltage
detection
1msec non-latched
1msec non-latched
Input AC Under voltage
detection
1msec non-latched
1msec non-latched
Input AC Over Current
1msec latched
1msec latched
Input AC fused
Input AC GFCI
GFCI module range 30 mA.
GFCI module range 30 mA.
Output DC over voltage
570 VDC latched
570 VDC latched
Output DC short circuit
Shut down
Shut down
CAN communication loss
1 sec shut down upon loss of
connection
1 sec shut down upon loss of
connection
AC input surge
6 KV requirement per UL 2231,
EMC requirements
6 KV requirement per UL 2231,
EMC requirements
External Remote E-Stop
Remove high power if external
E-stop is activated
Remove high power if external
E-stop is activated
AC Converter – Input terminal block
A Single AC input terminal block is used to connect the AC utility to the AC to DC Power Converter
AC Line Side
Load Side
Wire Range
Opening per pole
Wire Range
Opening per pole
350-6
2
350-6
2
Torque for all poles: 275 LB-IN