CRYSTAL CLEAN AIR
TM
GENERAL INSTALLATION GUIDELINES
8
BSE, Inc., 2246 Palmer Drive, Suite 108, Schaumburg, IL 60173
T: 866-360-5675 email: [email protected] web: www.bsesales.com
•
The recommended height top is not to exceed
11
feet
from the floor.
Ionization Placement &
Clearance
BSE units should not be located near to air exhausting inlets of other HVAC equipment. Supply air
outlets can be configured to aid the ionized air disbursement in a uniform manner. Ionizer should
be oriented such that the outlet is slightly below any ceiling fans. Exhaust fan inlets or other return
air points creating a negative pressure should not be within 4.5 times the width of the ionization
unit. Proper systems orientation will provide an enhancement to the Indoor Air Quality (IAQ) and
occupant comfort.
Figure 8: Installing BA-350.
Required Clearances for Mini
Figure 9: Installing BA-350.
Required Clearances for BA-350
See the figure on the left for required clearance
distances around an installed Mini wall-mounted unit.
•
There must be a minimum clearance of 2 inches
from the top of the Mini unit to the ceiling.
•
Clearance gap between any wall or enclosure and
the left or right side of the unit must be greater
than 2 feet.
•
The base of the unit must be at least
7.0 feet
from
the floor for adequate disbursement.
•
The recommended height top is not to exceed
11
feet
from the floor.
Required Clearances for Max Ceiling
Mounted Unit
See the figure on the right for required distances around
Mini ceiling-mounted unit.
•
There must be placed slightly below any ceiling
fans.
•
The base of the unit must be at least
7.0 feet
from
the floor for adequate disbursement.
Inspection
2”
2'
2'